2018-02-16 13:39:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION.
  
 2) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS.
 FBC ENERGY CONSERVATION - SECT. R403.7.1 EQUIPMENT
 SIZING. HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES,
 BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF
 THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE
 SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN
 SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY
 FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER
 FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD
 KITCHEN AND BATHROOM EXHAUST SYSTEMS. NEW OR
 REPLACEMENT HEATING AND COOLING EQUIPMENT SHALL HAVE AN
 EFFICIENCY RATING EQUAL TO OR GREATER THAN THE MINIMUM
 REQUIRED BY FEDERAL LAW FOR THE GEOGRAPHIC LOCATION
 WHERE THE EQUIPMENT IS INSTALLED.
  
 3) PROVIDE A MECHANICAL EQUIPMENT SCHEDULE ON THE
 PLANS. FBC 107.3.5.1.4
  
 4) SPECIFY THE LOCATION OF THE THERMOSTAT ON THE PLANS.
 FBC 107.3.5.1.4
  
 5) SHOW COMPLIANCE WITH FBC M1507.2, WHICH REQUIRES THE
 BATH EXHAUST AIR TO BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.
  
 6) BLOWER DOOR TESTING IS REQUIRED FOR RESIDENTIAL
 BUILDINGS PERMITTED ON OR AFTER JULY 1, 2017.
  