2017-10-31 04:58:14 | 1) SHT. C 103 - IDENTIFY IN THE NARRATIVE THE SPECIFIC |
| CHANGES THAT HAVE BEEN MADE TO THIS DRAWING. WPB AMEND. |
| TO FBC SEC. 107.2.1. |
| 2) IRRIGATION SHEETS I101 & I102 - IDENTIFY IN THE |
| NARRATIVE THE SPECIFIC CHANGES THAT HAVE BEEN MADE TO |
| THESE DRAWINGS.WPB AMEND. TO FBC SEC. 107.2.1.A |
| REVISION APPLICATION SHOULD BE SUBMITTED UNDER THE |
| IRRIGATION PERMIT. |
| 3) SHT. A101C - SHOW THE LENGTH AND WIDTH DIMENSIONS OF |
| TOILET ROOM #168. SHOW THE WIDTH OF THE LAVATORY |
| COUNTERTOP, AND SHOW THE REQUIRED CLEAR FLOOR SPACE FOR |
| THE WATER CLOSET AND THE LAVATORY AND THE DIMENSIONS OF |
| EACH CLEAR FLOOR SPACE.COMPLY WITH 2010 |
| FBC-ACCESSIBILITY SECS. 604.3.1, 606.2. |
| 4) SHT.A103A - SHOW THE LENGTH AND WIDTH DIMENSIONS OF |
| TOILET ROOM #838. SHOW THE WIDTH OF THE LAVATORY |
| COUNTERTOP, AND SHOW THE REQUIRED CLEAR FLOOR SPACE FOR |
| THE WATER CLOSET AND THE LAVATORY AND THE DIMENSIONS OF |
| EACH CLEAR FLOOR SPACE.COMPLY WITH 2010 |
| FBC-ACCESSIBILITY SECS. 604.3.1, 606.2. |
| 5) SHT.A104A - SHOW THE WIDTH OF THE LAVATORY |
| COUNTERTOP IN TOILET ROOM #938.. |
| 6) SHT.A401A - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 7) SHT. A401B - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 8)SHT. A401B - ADA BATH - SHOW THE REQUIRED 60 INCHES |
| WIDE BY 56 INCHES DEEP CLEAR FLOOR SPACE FOR THE WATER |
| CLOSET PER THE FBC- ACCESSIBILITY SEC.233.3,809.4, |
| 604.3. |
| 9) SHT. A401C - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 10) SHT. A402 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. . |
| 11) SHT. A403 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 12) SHT. A404 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 13) SHT. A405 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 14) SHT. A406 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 15) SHT. A407 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 16) SHT. A408 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 17) SHT. A410 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 18) SHT. A412 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| PLAN. |
| 19) SHT. P101C - BREAKROOM #167 - THE CONDENSATE WASTE |
| CANNOT DISCHARGE TO THE HAND SINK/SANITARY SYSTEM PER |
| CITY OF WPB CODE OF ORDINANCES CHAPT. 90, SEC. 90-126 |
| (B) (5). |
| 20) SHT. P502 - THE DRAWING SHOWS THE DELETION OF TWO |
| RECIRCULATING PUMPS FOR THE HOT WATER RECIRCULATION |
| SYSTEM AND THE BOOSTER PUMP BEING USED TO SERVE THE |
| RECIRCULATION SYSTEM. THE WATER HEATER/STORAGE TANK |
| DETAIL STILL SHOWS A RECIRCULATION PUMP NEAR THE |
| AQUASTAT. SHOULD THIS BE IDENTIFIED AS THE BOOSTER |
| PUMP? CLARIFY. |
| 21) PLEASE CLARIFY WITH A NARRATIVE AS TO HOW THE |
| INSTALLATION OF A BOOSTER PUMP THAT WILL OPERTE WHEN |
| THE PRESURE FALLS BELOW 100 PSI WILL MEET THE INTENT OF |
| COMPLYING WITH 2010 FBC-PLUMBING SEC.607.2 FOR |
| MAINTAINING THE TEMPERATURE IN ACCORDANCE WITH THE 2010 |
| FBC-ENERGY CODE SEC. 504. THE PREVIOUS RECIRCULATING |
| PUMPS WERE WIRED TO AN AQUASTAT WHEREAS THE BOOSTER |
| PUMP APPEARS TO BE WIRED TO PRESSURE SENSORS. I AM |
| CONFUSED. PLEASE CLARIFY. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |