Plan Review Notes For Permit 17100833 |
Permit Number |
17100833 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-10-20 15:27:49 | 1ST REVIEW FBC-2014 BUILDING | | PERMIT #17100833 | | 10/20/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE INDICATE ON THE PLANS OR THE PERMIT | | APPLICATION THE TOTAL SQUARE FOOTAGES OF SHINGLE AND | | FLAT ROOFS TO BE REPLACED. | | | | 2) GAF RUBBEROID MODIFIED BITUMEN ROOF NOA #14-1030.02: | | PLEASE IDENTIFY WHICH OF THE APPROVED ASSEMBLIES IS TO | | BE INSTALLED AND SEE LIMITATION #7 WHCIH REQUIRES | | ENGINEERED CALCULATIONS BY A FL. LICENSED P.E. FOR | | ENHANCED FASTENER DENSITIES AT THE PERIMETER AND CORNER | | AREAS OF THE ROOF. | | | | CHRISTOPHER L. COLE | | BUILDING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|