Plan Review Notes
Plan Review Notes For Permit 17100824
Permit Number 17100824
Review Stop G
Sequence Number 3
Notes
Date Text
2018-08-29 14:16:13GAS APPROVED UNDER PERMIT APPLICATION #18020723. OK TO
 RELEASE THE MASTER. TKL.
2018-02-13 05:23:501) SUBMIT A SEPARATE PERMIT APPLICATION FOR THE GAS AND
 A SEPARATE PERMIT APPLICATION FOR THE PLUMBING
 CONNECTIONS TO THE TANKLESS WATER HEATER INSTALLATION
 AND FOR THE NEW WATER LINES TO BE RUN. . WPB AMEND. TO
 FBC SEC. 107.1. 3RD REQUEST.
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED ABOVE
 GROUND.TO THE TANKLESS WATER HEATER.WPB AMENDMENTS TO
 FBC SEC.107.2.1. 3RD REQUEST.
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3. 3RD REQUEST.
 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. 3RD REQUEST
 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THE TANKLESS WATER HEATER.THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.3RD REQUEST.
 6) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. 3RD REQUEST.
 7) TWO COPIES OF A GAS SIZING TABLE FOR THE GAS HAS
 BEEN SUBMITTED BUT THERE IS NO STANDARD OR INFORMATION
 AS TO WHERE THIS TABLE IS FROM. THE TABLE NOTES IT IS
 FOR NATURAL GAS AND PROPANE BOTH WHICH DO NOT CORRELATE
 WITH THE SIZING TABLE IN THE 2014 FBC-FUEL GAS CODE.
 CLARIFY.
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM ( PE PIPE) OR PLACE A NOTE
 ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC.
 G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3.3RD
 REQUEST
 9) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE PIPE
 BEING INSTALLED ABOVE GROUND.. COMPLY WITH 2014
 FBC-FUEL GAS.3RD REQUEST.
  
 **NOTE- NONE OF THE PREVIOUS GAS COMMENTS HAVE BEEN
 ADDRESSED. RESUBMITTAL OF THESE PLANS WILL BE SUBJECT
 TO A RESUBMITTAL PAYMENT OF 4 TIMES THE FEE APPLIED TO
 PLAN REVIEW PER FL. STATUTE 553.80 (2) (B). DO NOT
 RESUBMIT THESE PLANS UNTIL ALL PLAN REVIEW COMMENTS
 HAVE BEEN ADDRESSED.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  