2017-10-27 15:14:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO DIMENSIONS INDICATED OF THE WIDTH OF
 THE DRIVE LANESOF THE SOUTH GATE. FIRE DEPARTMENT
 VEHICLES SHALL HAVE UNRESTRICTED ACCESS WIDTH OF A
 MINIMUM 12'.
  
 PLEASE PROVIDE THE DIMENSION TO THE EDGE OF THE BOLLARD
 FROM BOTH CURBS.
  
  
  
 2) THERE IS NO INDICATIONS OF HOW THE FIRE DEPARTMENT
 WILL GAIN ACCESS THROUGH THESE GATES; 24 HOUR EMERGENCY
 ACCESS IS REQUIRED. A KNOX KEY SWITCH IS REQUIRED FOR
 ACCESS.
  
 PLEASE PROVIDE DETAILS ON HOW THE FD WILL GAIN ACCESS
 THRU THESE GATES AND/ OR PROVIDE A KNOX KEY SWITCH AT
 EACH LOCATION.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  