Plan Review Notes
Plan Review Notes For Permit 17100790
Permit Number 17100790
Review Stop G
Sequence Number 3
Notes
Date Text
2017-11-28 13:57:2011/28/2017 GAS 3RD REVIEW **DENIED**
  
  
 COMMENTS FROM LAST REVIEW HAVE NOT BEEN ADDRESSED. IT
 IS RECOMMENED YOU CONTRACT THIS PLAN REVIEWER. A 4TH
 DENIED PLAN REVIEW WILL RESULT IN A 4XFEE FOR PLAN
 REVIEW
  
  
 1) A PROPER GAS ISOMETRIC RISER DIAGRAM SHOWING THE TIE
 IN SIZE TO THE EXISTING SYSTEM WITH THE CONNECTION TO
 THE GAS VALVE, REGULATOR AND DRIP LEG AT THE GENERATOR.
 FBC 107.3.5.THE PLANS INDICATE AN EXISTING GAS METER.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION
  
 2) YOUR SIZING TABLE IS THE INCORRECT CHART. IT SHOULD
 BE SCH 40 METALLIC PIPING AT .5 LBS FGC 402.3. SUBMIT
 TWO COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE
 THE GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS
 SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4,
 401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2014 FBC-RES. SEC. G2412.4, G2412.8, G2413.1,
 G2413.2, & G2413.3
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  