2017-10-31 15:05:29 | 10/31/2017 1ST GAS REVIEW**DENIED** |
| |
| 1) SLAB DETAIL DRAWNING IS REQUIRED TO HAVE A WET SIGN/ |
| SEAL PER FL ADMIN RULE 61G15-23.001. ALSO YOUR P.E |
| RONALD WILSON LICENSE #9710 PER (MYFLORIDALICENSE.COM) |
| HAS BEEN REVOKED SINCE FEB,2017 AND THIS REVIEWER HAS |
| ALREADY ADVISED YOU OF SUCH PAST REVIEWS. |
| |
| 2) YOU MUST INCLUDE EXISTING BTU LOADS ON THE SYSTEM |
| AND INCLUDE THEM ON THE ISOMETRIC DRAWNING. THE PLANS |
| INDICATE AN EXISTING GAS METER. THE BTU LOAD OF THE |
| EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST |
| BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A |
| GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF |
| EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE |
| PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| THE SECTION.. FGC SECS. 401.4, 401.8, 402.1, 402.2, |
| 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2, |
| G2413.3. |
| |
| 3) YOU MUST INCLUDE ALL SIZING TABLES (2 COPIES) FOR |
| EACH PIPING MATERIAL BEING USED OR EXISTING. YOU HAVE |
| ONLY PROVIDED THE SIZING TABLE FOR P.E PIPING. SUBMIT |
| TWO COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE |
| THE GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS |
| SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR |
| OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS |
| SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4, |
| 401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) |
| OR 2014 FBC-RES. SEC. G2412.4, G2412.8, G2413.1, |
| G2413.2, & G2413.3 |
| |
| TIM HUNT |
| PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| 561-805-6695 |
| [email protected] |