Plan Review Notes For Permit 17100790 |
Permit Number |
17100790 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-11-01 06:31:04 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF SIGNED, SEALED AND DATED | | GENERATOR PAD AND ANCHORING DETAILS FOR EXPOSURE | | CATEGORY C AND A 170 MPH VULT WIND SPEED. THE DOCUMENTS | | ARE REQUIRED TO HAVE THE ENGINEER'S ORIGINAL | | HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE | | NOT ACCEPTABLE. FAC 61G15 - 23.002 | | | | 2) THE ENGINEER THAT IS ON THE SLAB ANCHORING PLANS, | | RONALD H. WILSON P.E. LICENSE NO. 9710, HAS HAD HIS FL | | ENGINEERING LICENSE REVOKED SINCE 2/28/2017. SUBMIT | | PLANS FROM A CURRENTLY LICENSED FL ENGINEER. FS 471 | | |
|