Plan Review Notes
Plan Review Notes For Permit 17100775
Permit Number 17100775
Review Stop E
Sequence Number 7
Notes
Date Text
2018-04-16 16:49:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN
 NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN
 ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL
 COMMENTS IN PARENTHESES.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2 (NOT PROVIDED)(NOT PROVIDED ON 5TH
 REVIEW)(STILL NOT PROVIDED ON 6TH REVIEW)(7TH REVIEW -
 SOME OCCUPANCY SENSORS WERE ADDED, BUT NOT ALL LIGHTS
 SHOW THE AUTOMATIC CONTROL REQUIRED PER CODE.)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION
 PROVIDED SHOWS DEMAND FACTORS THAT ARE NOT PERMITTED
 PER CODE. PROVIDE ACCURATE LOAD CALCULATION.)(LOAD
 CALCULATION STILL NOT PER CODE ON 5TH REVIEW.)(STILL
 NOT CORRECT ON 6TH REVIEW. THE WATER HEATER LOAD CAN
 NOT BE CALCULATED AT 50%. WHEN CALCULATED AT 100%, THE
 EXISTING SERVICE IS TOO SMALL. PROVIDE CORRECTION.)(7TH
 REVIEW - LOAD CALCULATION STILL NOT CORRECT. A FEEDER
 MUST BE SIZED TO HANDLE 125% OF THE CONTINUOUS LOAD
 PLUS 100% OF THE NON-CONTINUOUS LOAD. YOU HAVE NOT
 CORRECTLY ADDED ALL CONTINUOUS LOADS. PANEL B IS SHOWN
 WITH A LOAD THAT EXCEEDS THE FEEDER SIZE AND OCP SIZE.
 MAIN SERVICE LOAD MAY ALSO EXCEED THE FEEDER SIZE AND
 OCP WHEN COMPLETED CORRECTLY. WHEN LOAD CALCULATION IS
 ACCURATE, THIS WILL BE USED TO SIZE FEEDERS AND OCP FOR
 PANELS.)
 7. CORRECTED.
 8. CORRECTED.
 9. FEE ADDED.
 10. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved