2018-04-03 15:13:13 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN |
| NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN |
| ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL |
| COMMENTS IN PARENTHESES. |
| |
| 1. CORRECTED. |
| 2. CORRECTED. |
| 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2, |
| 405.2.2.2 (NOT PROVIDED)(NOT PROVIDED ON 5TH |
| REVIEW)(STILL NOT PROVIDED ON 6TH REVIEW) |
| 4. CORRECTED. |
| 5. CORRECTED. |
| 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION |
| PROVIDED SHOWS DEMAND FACTORS THAT ARE NOT PERMITTED |
| PER CODE. PROVIDE ACCURATE LOAD CALCULATION.)(LOAD |
| CALCULATION STILL NOT PER CODE ON 5TH REVIEW.)(STILL |
| NOT CORRECT ON 6TH REVIEW. THE WATER HEATER LOAD CAN |
| NOT BE CALCULATED AT 50%. WHEN CALCULATED AT 100%, THE |
| EXISTING SERVICE IS TOO SMALL. PROVIDE CORRECTION.) |
| 7. CORRECTED. |
| 8. CORRECTED. |
| 9. FEE ADDED. |
| 10. CORRECTED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |