2018-03-17 08:13:19PLUMBING PROVISO:
 REQUIRED BEFORE FIRST ROUGH INSPECTION.
 1. PROVIDE A SERVICE SINK PER FBC EX 1010.1 AND FBC PL
 TABLE 403.1
 2. PROVIDE A WATER FOUNTAIN FBC PL TABLE 403.1 SHALL
 COMPLY WITH FBC ACC 211.2
 3. WATER HEATER SHALL BE SIZED TO PROVIDE HOT WATER TO
 ALL FIXTURES AT PEAK LOAD PROVIDE MANUFACTURE
 SPECIFICATIONS ON JOBSITE FOR INSPECTIONS. PER WPB
 AMEND TO FBC 107.2.1 AND FBC PL 607.1
  