Plan Review Notes
Plan Review Notes For Permit 17100775
Permit Number 17100775
Review Stop E
Sequence Number 4
Notes
Date Text
2018-02-28 09:53:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN
 NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN
 ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL
 COMMENTS IN PARENTHESES.
  
 1. ELECTRICAL NOTES REFERENCES THE 2009 NEC, WHICH
 DOESN'T EXIST. PROVIDE CORRECT CODE REFERENCE. FBC
 PREFACE (MUST BE CORRECTED TO CURRENT CODE)
 2. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5 (MUST BE ON PLAN)
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2 (NOT PROVIDED)
 4. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 (INDICATE NEW OR EXISTING CIRCUITS,)
 5. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 (NOT PROVIDED)
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION
 PROVIDED SHOWS DEMAND FACTORS THAT ARE NOT PERMITTED
 PER CODE. PROVIDE ACCURATE LOAD CALCULATION.)
 7. CORRECTED.
 8. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 WITHIN 6 FEET OF A SINK. NEC 210.8 (NOT CORRECTED.)
 9. FEE ADDED.
 10. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC EC C405.2.4 (NOT PROVIDED)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  