2018-02-28 09:53:30 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN |
| NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN |
| ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL |
| COMMENTS IN PARENTHESES. |
| |
| 1. ELECTRICAL NOTES REFERENCES THE 2009 NEC, WHICH |
| DOESN'T EXIST. PROVIDE CORRECT CODE REFERENCE. FBC |
| PREFACE (MUST BE CORRECTED TO CURRENT CODE) |
| 2. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| CODE. FBC CE 405.5 (MUST BE ON PLAN) |
| 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2, |
| 405.2.2.2 (NOT PROVIDED) |
| 4. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR |
| ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 |
| (INDICATE NEW OR EXISTING CIRCUITS,) |
| 5. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| 250.94, 408.30 (NOT PROVIDED) |
| 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION |
| PROVIDED SHOWS DEMAND FACTORS THAT ARE NOT PERMITTED |
| PER CODE. PROVIDE ACCURATE LOAD CALCULATION.) |
| 7. CORRECTED. |
| 8. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS |
| WITHIN 6 FEET OF A SINK. NEC 210.8 (NOT CORRECTED.) |
| 9. FEE ADDED. |
| 10. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC |
| 600.5; FBC EC C405.2.4 (NOT PROVIDED) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |