2018-01-29 15:04:19 | 3RD REVIEW FBC-2014 MECHANICAL |
| FBC-14 ENERGY CONSERVATION CODE |
| FBC-14 EXISTING BUILDING CODE |
| PERMIT #17100775 |
| 1/19/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE REVISED MECHANICAL PLANS ARE NOT IN COMPLIANCE. |
| I HAVE REPRINTED THE COMMENTS FROM THE 1ST AND 2ND |
| REVIEWS BELOW. THE ISSUE IS THE REQUIRED SOURCE CAPTURE |
| SYSTEM AT EACH NAIL STATION HAS NOT YET BEEN PROVIDED. |
| THE EXHAUST IN THE SOFFIT AND IN THE CEILING OVER THE |
| PEDICURES DOES NOT MEET COMPLIANCE FOR CAPTURING AT THE |
| SOURCE. IN ADDITION, THE REQUIRED BEAUTY SALON |
| |
| EXHAUST SYSTEM FOR THE SALON AT A RATE OF 0.60 CFMS PER |
| SQ. FT., AND THE REQUESTED EXHAUST CALCULATION FOR THE |
| SALON HAVE NOT BEEN PROVIDED. |
| |
| 2ND REVIEW FBC-2014 MECHANICAL |
| FBC-14 ENERGY CONSERVATION CODE |
| FBC-14 EXISTING BUILDING CODE |
| PERMIT #17100775 |
| 12/27/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) COMMENT #4 FROM THE 1ST REVIEW WAS NOT ADDRESSED AND |
| STILL EXISTS. I HAVE REPRINTED IT BELOW. PLEASE REVISE |
| THE PLANS TO SHOW COMPLIANCE. |
| |
| 4) REFER TO TABLE 403.3 FBC-14 MECHANICAL AND PROVIDE |
| EXHAUST VENTILATION CALCULATIONS FOR THE NAIL SALON AND |
| BEAUTY SALON. EACH IS REQUIRED TO HAVE AN EXHAUST |
| AIRFLOW RATE OF 0.60 CFMS PER SQ. FT., AND MUST COMPLY |
| WITH FOOTNOTES B & H: RECIRCULATION OF AIR FROM THE |
| SPACES IS PROHIBITED, AND EACH NAIL STATION SHALL BE |
| PROVIDED WITH A SOURCE CAPTURE SYSTEM CAPABLE OF |
| EXHAUSTING NOT LESS THAN 50 CFM PER STATION. |
| ADDITIONALLY, PLEASE PROVIDE OUTSIDE AIR CALCULATIONS |
| FOR THE OCCUPANTS IN THE TENANT SPACE AS REQUIRED BY |
| TABLE 403.3: PROVIDE A SCHEDULE THAT INDICATES THE |
| REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |