2018-01-29 15:04:193RD REVIEW FBC-2014 MECHANICAL
 FBC-14 ENERGY CONSERVATION CODE
 FBC-14 EXISTING BUILDING CODE
 PERMIT #17100775
 1/19/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED MECHANICAL PLANS ARE NOT IN COMPLIANCE.
 I HAVE REPRINTED THE COMMENTS FROM THE 1ST AND 2ND
 REVIEWS BELOW. THE ISSUE IS THE REQUIRED SOURCE CAPTURE
 SYSTEM AT EACH NAIL STATION HAS NOT YET BEEN PROVIDED.
 THE EXHAUST IN THE SOFFIT AND IN THE CEILING OVER THE
 PEDICURES DOES NOT MEET COMPLIANCE FOR CAPTURING AT THE
 SOURCE. IN ADDITION, THE REQUIRED BEAUTY SALON
  
 EXHAUST SYSTEM FOR THE SALON AT A RATE OF 0.60 CFMS PER
 SQ. FT., AND THE REQUESTED EXHAUST CALCULATION FOR THE
 SALON HAVE NOT BEEN PROVIDED.
  
 2ND REVIEW FBC-2014 MECHANICAL
 FBC-14 ENERGY CONSERVATION CODE
 FBC-14 EXISTING BUILDING CODE
 PERMIT #17100775
 12/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #4 FROM THE 1ST REVIEW WAS NOT ADDRESSED AND
 STILL EXISTS. I HAVE REPRINTED IT BELOW. PLEASE REVISE
 THE PLANS TO SHOW COMPLIANCE.
  
 4) REFER TO TABLE 403.3 FBC-14 MECHANICAL AND PROVIDE
 EXHAUST VENTILATION CALCULATIONS FOR THE NAIL SALON AND
 BEAUTY SALON. EACH IS REQUIRED TO HAVE AN EXHAUST
 AIRFLOW RATE OF 0.60 CFMS PER SQ. FT., AND MUST COMPLY
 WITH FOOTNOTES B & H: RECIRCULATION OF AIR FROM THE
 SPACES IS PROHIBITED, AND EACH NAIL STATION SHALL BE
 PROVIDED WITH A SOURCE CAPTURE SYSTEM CAPABLE OF
 EXHAUSTING NOT LESS THAN 50 CFM PER STATION.
 ADDITIONALLY, PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 FOR THE OCCUPANTS IN THE TENANT SPACE AS REQUIRED BY
 TABLE 403.3: PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  