Plan Review Notes
Plan Review Notes For Permit 17100775
Permit Number 17100775
Review Stop B
Sequence Number 3
Notes
Date Text
2018-01-26 08:50:392014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100775
 ADD: 525 25TH ST.
 CONT: TOU INC.
 TEL: 561-255-1417
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. JAN. 26/2018
 ACTION: DENIED
  
 HOLD ON PERMIT!!!!! STILL NEED OWNERS SIGNATURE ON THE
 PERMIT APPLICATION!!!!
  
 1-3) COMPLIED.
  
 4) PROVISO: SHEET AE-1.0 ALSO INDICATES A RECEPTIONIST/
 CASHIER SERVICE COUNTER BUT THERE ARE NO DETAILS
 PROVIDING CODE COMPLIANCE FOR THE 2014
 FBC-ACCESSIBILITY CODE SECTIONS:
 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK
 WRITING SURFACES SHALL COMPLY WITH 902.3.
 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) 3RD REQUEST. THE SHEET AE 3.0 STILL DOES NOT SHOW
 COMPLIANCE WITH THE MECHANICAL CODE, I DISCUSSED THIS
 WITH THE MECHANICAL PLANS EXAMINER, DEPENDING ON THE
 NEXT GENERATION OF PLANS THIS COMMENT STILL STANDS.
 THERE MAY BE SOFFITS TO BE BUILT TO HIDE EXHAUST AIR
 DUCTWORK AND OR ROOF TOP PENETRATIONS.
  
 THE MANICURES AND PEDICURES HAVE TO CATCH THE FUMES AT
 THE SOURCE, PLEASE REVIEW THE MECHANICAL COMMENT # 4
 WILL NEED TO COMPLY WITH 2014 FBC-M TABLE 403,
 FOOTNOTES B & H, DEPENDING WHERE YOU BRING IN THE
 MAKE-UP AIR AND EXHAUST AIR YOU WILL HAVE EITHER WALL
 OR ROOF PENETRATIONS FOR THE NEW INTAKE AND EXHAUST
 FANS. PLEASE NOTE THERE MAYBE ADDITIONAL COMMENTS ABOUT
 ROOF TOP CURBS, INTAKE AND EXHAUST FANS AND THE
 ANCHORING OF THESE UNITS TO THE CURRENT WIND LOADS
 BECAUSE OF CODE REQUIREMENTS UNDER THE MECHANICAL CODE.
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  