Date |
Text |
2018-01-04 11:09:21 | 2ND REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED. |
| |
| 4. A DRINKING FOUNTAIN IS REQUIRED PER FBC PL TABLE |
| 403.1 |
| |
| 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1 |
| |
| 6. PLEASE PROVIDE THE DIMENSIONS OF ACCESSIBLE BATHROOM |
| TO CHECK LEVEL OF ACCESSIBILITY. PER WPB AMEND TO FBC |
| 107.2.1 PARTIALLY COMPLIED PLEASE PROVIDE MOUNTING |
| DETAILS FOR GRAB BARS, SINK, TOILET AND MIRROR, TOILET |
| PAPER DISPENSER. |
| |
| 7. THE DRAIN TO THE WASHING MACHINE SHALL BE 3" PER FBC |
| PL 406.2 SHOW TRAP AND STAND PIPE ON ISOMETRIC DRAWING. |
| |
| 8. A LENT TRAP IS REQUIRED ON WASHING MACHINE DRAIN. |
| PER FBC PL 1003.6 |
| |
| 9. PLEASE PROVIDE MANUFACTURE INSTALLATION GUIDES FOR |
| PEDICURE CHAIRS AND SHAMPOOOO SINKS. PER WPB AMEND TO |
| FBC 107.2.1 PARTIALLY COMPLIED INSTALL DETAILS FOR |
| PEDICURE CHAIRS ARE NOT LEGIBLE. INSTALLATION GUIDE FOR |
| SHAMPO SINK NOT PROVIDED PAPER WORK THAT WAS PROVIDED |
| DID NOT GIVE ANY INFORMATION ON PLUMBING CONNECTIONS. |
| PROVIDE TWO COPY'S OF BOTH. |
| |
| 10. PROVIDE A DETAIL FOR THE CONNECTIONS ON THE |
| PEDICURE CHAIRS. PER WPB AMEND TO FBC 107.2.1 |
| |
| 11. THE SHAMPOO SINKS ARE LABELED AS HAND SINKS ON THE |
| SANITARY RISER DIAGRAM PLEASE CLARIFY. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 12. THE SANITARY RISER DIAGRAM IS MISSING THE SIZE ON |
| SOME OF THE PIPES PLEASE SIZE ALL PIPES ON RISER. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| NEW COMMENTS |
| |
| 1. BACKFLOW PROTECTION IS REQUIRED FOR PEDICURE CHARS |
| AND SHAMPO SINKS. PER FBC PL 608.2 |
| |
| 2. IT APPEARS THERE IS A 1/2" WATER MAIN SUPPLING SPACE |
| THEN INCREASING SIZE TO 3/4 PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 3. THE WATER HEATER HAS A INLET AND OUTLET PIPE OF 1/2" |
| IS THIS CORRECT YOUR SUPPLING ALL FIXTURES WITH 1/2" |
| HOT WATER SUPPLY. PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 4. THE PEDICURE CHAIR DRAINS SHALL BE TRAPPED. PER FBC |
| PL 1002.1 |
| |
| 5. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |