2017-11-01 12:54:01 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING, ENERGY |
| CONSERVATION CODES. |
| PERMIT #17100775 |
| 11/1/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET AE-1.0: APPLICABLE CODES MISSING INCLUDE- THE |
| FBC-14 FIFTH EDITION MECHANICAL, PLUMBING, ENERGY, AND |
| EXISTING BUILDING CODES. |
| |
| 2) AE-1.0: THE PROPOSED PROJECT IS CLASSIFIED AS A |
| CHANGE OF OCCUPANCY IN COMPLIANCE WITH SECTION 202 |
| FBC-14 EXISITNG BUILDING CODE. PLEASE INCLUDE THIS |
| DESCRIPTION UNDER PROJECT/OCCUPANCY DATA. |
| |
| 3) REFER TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION |
| AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT FOR |
| THE CHANGE OF OCCUPANCY. SEE SECTIONS C101.5 & C401.2 |
| FOR SUBMITTALS AND COMPLIANCE PATH INFORMATION. |
| |
| 4) REFER TO TABLE 403.3 FBC-14 MECHANICAL AND PROVIDE |
| EXHAUST VENTILATION CALCULATIONS FOR THE NAIL SALON AND |
| BEAUTY SALON. EACH IS REQUIRED TO HAVE AN EXHAUST |
| AIRFLOW RATE OF 0.60 CFMS PER SQ. FT., AND MUST COMPLY |
| WITH FOOTNOTES B & H: RECIRCULATION OF AIR FROM THE |
| SPACES IS PROHIBITED, AND EACH NAIL STATION SHALL BE |
| PROVIDED WITH A SOURCE CAPTURE SYSTEM CAPABLE OF |
| EXHAUSTING NOT LESS THAN 50 CFM PER STATION. |
| ADDITIONALLY, PLEASE PROVIDE OUTSIDE AIR CALCULATIONS |
| FOR THE OCCUPANTS IN THE TENANT SPACE AS REQUIRED BY |
| TABLE 403.3: PROVIDE A SCHEDULE THAT INDICATES THE |
| REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. |
| |
| DUE TO THE DEFICIENCIES IN THE PLANS LISTED ABOVE, THE |
| 1ST REVIEW IS STOPPED PENDING RESUBMITTAL OF CORRECTED |
| CODE-COMPLIANT PLANS. PLEASE NOTE THAT PLANS DESIGNED |
| BY A QUALIFIED FL. LICENSED MECHANICAL ENGINEER WOULD |
| HELP EXPEDITE THE REVIEW AND PERMITTING PROCESS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |