2017-10-20 10:58:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET AE 1.0 & LS 1.0 - THERE IS ARE INDICATIONS |
| THAT THIS IS A MERCANTILE OCCUPANCY WITH AND OCCUPANCY |
| LOAD OF 30ST/PERSON OR 27 TOTAL OCCUPANTS. |
| |
| ACCORDING TO THE FFPC, NPFA 101, THIS IS A BUSINESS |
| OCCUPANCY.WITH AN OCCUPANCY LOAD OF 100 SF/PERSON, OR |
| 10. |
| |
| PER CHAPTER 3, DEFINITIONS - 3.3.188.3* BUSINESS |
| OCCUPANCY. AN OCCUPANCY USED FOR THE TRANSACTION OF |
| BUSINESS OTHER THAN MERCANTILE. |
| |
| FOR GUIDANCE PURPOSES, ACCORDING TO THE APPENDIX - |
| |
| A.3.3.188.3 BUSINESS OCCUPANCY. BUSINESS OCCUPANCIES |
| INCLUDE THE FOLLOWING: |
| (1) AIR TRAFFIC CONTROL TOWERS (ATCTS) |
| (2) CITY HALLS |
| (3) COLLEGE AND UNIVERSITY INSTRUCTIONAL BUILDINGS, |
| CLASSROOMS |
| UNDER 50 PERSONS, AND INSTRUCTIONAL LABORATORIES |
| (4) COURTHOUSES |
| (5) DENTISTS? OFFICES |
| (6) DOCTORS? OFFICES |
| (7) GENERAL OFFICES |
| (8) OUTPATIENT CLINICS (AMBULATORY) |
| (9) TOWN HALLS |
| |
| SERVICE FACILITIES COMMON TO CITY OFFICE BUILDINGS, |
| SUCH AS NEWSSTANDS, LUNCH COUNTERS SERVING FEWER THAN |
| 50 PERSONS, BARBER SHOPS, AND BEAUTY PARLORS ARE |
| INCLUDED IN THE BUSINESS OCCUPANCY GROUP. |
| |
| A NAIL SALON, THIS OCCUPANCY, FALLS UNDER THIS |
| OCCUPANCY DEFINITION. |
| |
| ACCORDING TO CHAPTER 7, MEANS OF EGRESS, |
| |
| 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE |
| NUMBER OF PERSONS DETERMINED BY DIVIDING THE FLOOR AREA |
| ASSIGNED TO THAT USE BY THE OCCUPANT LOAD FACTOR FOR |
| THAT USE AS SPECIFIED IN TABLE 7.3.1.2, FIGURE |
| 7.3.1.2(A), AND FIGURE 7.3.1.2(B). WHERE BOTH GROSS AND |
| NET AREA FIGURES ARE GIVEN FOR THE SAME OCCUPANCY, |
| CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA |
| FIGURE TO THE GROSS AREA OF THE PORTION OF THE BUILDING |
| DEVOTED TO THE USE FOR WHICH THE GROSS AREA FIGURE IS |
| SPECIFIED AND BY APPLYING THE NET AREA FIGURE TO THE |
| NET AREA OF THE PORTION OF THE BUILDING DEVOTED TO THE |
| USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED. |
| |
| TABLE 7.3.1.2 OCCUPANT LOAD FACTOR INDICATES AN |
| OCCUPANCY LOAD FACTOR OF 100 SQ FT/PERSON. |
| |
| PLEASE REVIEW AND CORRECT OR PROVIDED DETAIL |
| JUSTIFICATION. |
| |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |