Plan Review Notes
Plan Review Notes For Permit 17100767
Permit Number 17100767
Review Stop P
Sequence Number 4
Notes
Date Text
2019-12-10 11:38:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2014
 5TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 4TH REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. IT APPEARS THAT THERE HAS NOT BEEN A PLUMBING PERMIT
 APPLIED FOR OR EXECUTED FOR THIS STRUCTURE.
  
 2. PROVIDE AS REQUIRED BY THE PLUMBING OFFICIAL, ANY
 DOCUMENTATION INCLUDING OPENING OF WALLS, SLAB AND/OR
 VIDEO OF EXISTING PLUMBING INFRASTRUCTURE TO SHOW
 COMPLIANCE WITH THE 2014 FLORIDA PLUMBING CODE
  
 3. PLUMBING RISER NOTED AS EXISTING IS NOT CODE
 COMPLIANT.
 A. PER WPB FBC 107.2.1 AND 107.3.5.1.3, CLEARLY SHOW
 ALL FIXTURE DRAINS AND THEIR RESPECTIVE TRAPS (SEE THE
 SHOWER) AND ACTUAL LAYOUT OF WET VENT AND BUILDING
 DRAIN.
 B. IN ACCORDANCE WITH FBC PL 904.1, A MINIMUM OF ONE
 (1) VENT SHALL EXTEND TO THE OUTSIDE.
  
 3. PER WPB FBC 107.2.1, PROVIDE DETAILS AS NOTED IN THE
 FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION THE
 FOLLOWING;
 603.3 MIRRORS, 604.2 LOCATION, 604.3 CLEARANCE, 604.5.1
 SIDE WALL GRAB BARS, 604.5.2 REAR WALL GRAB BARS, 604.6
 FLUSH CONTROLS, 604.7 DISPENSERS, 606.2 LAVATORY CLEAR
 FLOOR SPACE, 606.3 LAVATOTY HEIGHT, 608.2.2 STD ROLL-IN
 SHOWERS, 608.3.2 GRAB BARS FOR STD ROLL-IN SHOWERS,
 608.5.2 SHOWER CONTROLS, 608.7 THRESHOLDS.
  
 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION SHEETS AND MANUFACTURER?S INSTALLATION
 REQUIREMENTS FOR THE NOTED INSTA-HOT WATER HEATER.
 INDICATE MODEL NUMBER, ELECTRICAL CHARACTERISTICS,
 MOUNTING DETAILS AND TYPE (TANK TYPE OR TANKLESS). IF
 TANKLESS, PROVIDE THE GPM. TANKLESS SHALL BE INSTALLED
 IN ACCORDANCE WITH MANUFACTURER?S RECOMMENDATION AND
 APPLICABLE REQUIREMENTS OF FBC PL CHAPTER 5. IF TANK
 TYPE, PROVIDE STORAGE CAPACITY AND TYPE AND SIZE OF
 THERMAL EXPANSION CONTROL AS REQIRED BY FBC PL 607.3.
 TANK TYPE SHALL BE INSTALLED IN ACCORDANCE WITH
 MANUFACTURER?S RECOMMENDATION AND SHALL BE PROVIDED
 WITH VALVES AND SAFETY DEVICES AS REQUIRED BY FBC PL
 503.1, 504.1, 504.2, 504.3, 504.4, 504.4.1, 504.5,
 504.6 (1-13), 504.7, 504.7.1, 504.7.2 AND FBC PL 607.3.
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM THE LAVATORY
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070.
 PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION FOR A TEMPERATURE LIMITING DEVICE FOR THE
 LAVATORY.
  
 6. PER WPB FBC 107.2.1 AND 107.3.5.1.3, SHOW ON THE
 FLOOR PLAN, THE ROUTING OF THE UNDERGROUND SANITARY TO
 THE EXTERIOR OF THE BUILDING.
  
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A WATER
 RISER DIAGRAM SHOWING THE COLD WATER SERVICE, COLD
 WATER DISTRIBUTION AND HOT WATER DISTRIBUTION. WATER
 HEATER SHALL BE SHOWN. PROVIDE SIZES TO SATISFY FIXTURE
 DEMAND TO COMPLY WITH FBC PL 604.3, 604.4 AND 604.5.
 MINIMUM SIZE OF DISTRIBUTION PIPING SHALL BE ? INCH
 NOMINAL IN ACCORDANCE WITH INDUSTRY STANDARDS. MINIMUM
 SIZE OF WATER SERVICE SHALL BE 3/4"INCH PIPING AND
 SHALL BE PROVIDED WITH A FULL SIZED VALVE AT THE
 ENTRANCE TO THE STRUCTURE PER FBC PL 606.1(2). SPECIFY
 AND PROVIDE A BACKFLOW PREVENTOR FOR THE WATER SERVICE
 IN ACCORDANCE WITH FBC PL 608.1.
  
 8. PER WPB FBC 107.2.1, SUBMIT A SITE PLAN SHOWING THE
 FOLLOWING:
 A. THE BUILDING SEWER ROUTING AND CONNECTION TO
 EXISTING SANITARY BUILDING DRAIN/SEWER COMPLYING WITH
 FBC PL 703.4, OR TO AN APPROVED CITY LATERAL.
 B. THE WATER SERVICE ROUTING AND CONNECTION TO EXISTING
 SITE WATER.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 17100767 4012 GARDEN AVE
  
  
  
  