Plan Review Notes For Permit 17100767 |
Permit Number |
17100767 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2019-12-10 15:34:31 | 4TH REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | WPB AMENDMENTS TO THE FBC. | | PERMIT #17100767 | | 12/10/19 | | | | PLAN REVIEW RESULTS: FAILED. | | | | | | REVISED PLANS HAVE BEEN SUBMITTED. THE GARAGE HAS BEEN | | CHANGED TO A CONFERENCE ROOM. | | | | THE REMAINING COMMENTS FROM THE THE PREVOUS THREE | | REVIEWS ARE LISTED BELOW- PLEASE COMPLY | | | | 1) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER | | THERE IS A NEW AC SYSTEM ON THE FLOOR PLAN DRAWINGS- | | SHEET A-1. | | | | A) PLEASE PROVIDE AN AC EQUIPMENT SCHEDULE. | | | | B) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | ROOMS AND SPACES EITHER USING NATURAL OR MECHANICAL | | MEANS- SEE SECTIONS 402, 403 AND TABLE 403.3. | | | | C) PROVIDE AC COOLING AND HEATING CALCULATIONS- | | C403.3.2 FBC-14 ENERGY COMPLIANCE. | | | | D) PROVIDE ENERGY CALCULATIONS- SECTION C101 AND | | C401.2. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|