Plan Review Notes
Plan Review Notes For Permit 17100767
Permit Number 17100767
Review Stop M
Sequence Number 4
Notes
Date Text
2019-12-10 15:34:314TH REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 WPB AMENDMENTS TO THE FBC.
 PERMIT #17100767
 12/10/19
  
 PLAN REVIEW RESULTS: FAILED.
  
  
 REVISED PLANS HAVE BEEN SUBMITTED. THE GARAGE HAS BEEN
 CHANGED TO A CONFERENCE ROOM.
  
 THE REMAINING COMMENTS FROM THE THE PREVOUS THREE
 REVIEWS ARE LISTED BELOW- PLEASE COMPLY
  
 1) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER
 THERE IS A NEW AC SYSTEM ON THE FLOOR PLAN DRAWINGS-
 SHEET A-1.
  
 A) PLEASE PROVIDE AN AC EQUIPMENT SCHEDULE.
  
 B) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 ROOMS AND SPACES EITHER USING NATURAL OR MECHANICAL
 MEANS- SEE SECTIONS 402, 403 AND TABLE 403.3.
  
 C) PROVIDE AC COOLING AND HEATING CALCULATIONS-
 C403.3.2 FBC-14 ENERGY COMPLIANCE.
  
 D) PROVIDE ENERGY CALCULATIONS- SECTION C101 AND
 C401.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  