2019-12-16 15:09:37 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE |
| COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. CORRECTED. |
| 2. CORRECTED. |
| 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 (NOT |
| PROVIDED. THIS IS FOR THE MAIN SERVICE THAT THE |
| SUB-PANEL IS FED FROM. LOAD IS BEING ADDED TO THIS AND |
| REVIEWER NEEDS TO KNOW THE CURRENT SIZE AND TOTAL |
| CALCULATED LOAD. ADDITIONALLY, THE LOAD CALCULATION |
| PROVIDED FOR THE PANEL IN THIS STRUCTURE IS NOT |
| COMPLETE, PROVIDE CORRECTION.) |
| 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, |
| 225.32 (NOT PROVIDED IN THE NOTES IT STATES THE 60 AMP |
| PANEL IS TO REMAIN, IN THE PANEL SCHEDULE IT STATES |
| THAT A NEW PANEL WILL BE INSTALLED. WHICH IS CORRECT? |
| CORRECT DISCREPANCY AND PROVIDE MAIN BREAKER IN PANEL |
| OR DISCONNECT AS PREVIOUSLY STATED.) |
| 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| CIRCUIT. NEC 250.32; FBC RE3607.3 (NOT PROVIDED.) |
| 6. CORRECTED. |
| 7. CORRECTED. |
| 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC |
| 110.3 (NOT PROVIDED.) |
| 9. CORRECTED. |
| 10. CORRECTED. |
| 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15 |
| AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC |
| RE3902.12 (NOT PROVIDED.) |
| |
| NEW COMMENT: |
| |
| 12. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE |
| NOT BEEN ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT |
| REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN |
| AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW |
| IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO |
| EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A |
| LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B) |
| THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $ 420.00, |
| BASED ON CURRENT VALUE OF PROJECT |
| 13. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| 109.3 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |