Plan Review Notes
Plan Review Notes For Permit 17100767
Permit Number 17100767
Review Stop E
Sequence Number 4
Notes
Date Text
2019-12-16 15:09:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE
 COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 (NOT
 PROVIDED. THIS IS FOR THE MAIN SERVICE THAT THE
 SUB-PANEL IS FED FROM. LOAD IS BEING ADDED TO THIS AND
 REVIEWER NEEDS TO KNOW THE CURRENT SIZE AND TOTAL
 CALCULATED LOAD. ADDITIONALLY, THE LOAD CALCULATION
 PROVIDED FOR THE PANEL IN THIS STRUCTURE IS NOT
 COMPLETE, PROVIDE CORRECTION.)
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32 (NOT PROVIDED IN THE NOTES IT STATES THE 60 AMP
 PANEL IS TO REMAIN, IN THE PANEL SCHEDULE IT STATES
 THAT A NEW PANEL WILL BE INSTALLED. WHICH IS CORRECT?
 CORRECT DISCREPANCY AND PROVIDE MAIN BREAKER IN PANEL
 OR DISCONNECT AS PREVIOUSLY STATED.)
 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3 (NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC
 110.3 (NOT PROVIDED.)
 9. CORRECTED.
 10. CORRECTED.
 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.12 (NOT PROVIDED.)
  
 NEW COMMENT:
  
 12. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $ 420.00,
 BASED ON CURRENT VALUE OF PROJECT
 13. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER