Plan Review Notes For Permit 17100767 |
Permit Number |
17100767 |
|
Review Stop |
NFIP |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-12-16 06:59:18 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | NATIONAL FLOOD INSURANCE PROGRAM REVIEW DENIED: | | | | IT APPEARS THAT REQUIRED FLOOD INFORMATION HAS NOT BEEN | | CONSIDERED. | | FOR THIS STRUCTURE A BREAK DOWN OF THE VALUATION IS | | REQUIRED AS IT APPEARS TO BE A SUBSTANTIAL IMPROVEMENT. | | | | MORE INFORMATION IS REQUIRED: | | | | 1. FBC B 107.2.1, PROVIDE THE SURVEYOR'S ELEVATION | | CERTIFICATE. | | 2. FBC B 107.2.1, PROVIDE A COMPLETED FORM BOARD SURVEY | | FOR THIS STRUCTURE. | | 3. FBC B 107.2.1/FBC B 109.3, PROVIDE A BREAK DOWN OF | | THE VALUATION, AS THIS APPEARS TO BE A SUBSTANTIAL | | IMPROVEMENT PER FEMA'S DEFINITION. | | | | |
|