2017-11-15 17:52:411ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 WPB AMENDMENTS TO THE FBC.
 PERMIT #17100767
 11/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE BUILDING PLAN REVIEWER HAS DETERMINED THAT NO
 PERMIT EXISTS FOR THE BUILDING AND AS A RESULT IT WILL
 BE REVIEWED AS A NEW BUILDING.
  
 2) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER
 THERE IS AN AIR HANDLER SHOWN IN A CLOSET BY THE
 OFFICE. PLEASE PROVIDE COMPLETE AC PLANS INCLUDING:
  
 A) AC EQUIPMENT SCHEDULE.
  
 B) DUCT LAYOUT PLAN.
  
 C) AIR DEVICE SCHEDULE.
  
 D) LOCATION OF CONDENSER AND FLOOD ELEVATION AND WIND
 RESISTANCE COMPLIANCE.
  
 3) CALCULATIONS REQUIRED:
  
 A) MINIMUM VENTILATION CALCULATIONS FOR THE OCCUPIED
 AREA EITHER USING NATURAL OR MECHANICAL MEANS- SEE
 SECTIONS 402, 403 AND TABLE 403.3
  
 B) AC COOLING AND HEATING CALCULATIONS- C403.3.2 FBC-14
 ENERGY COMPLIANCE.
  
 C) ENERGY CALCULATIONS- SECTION C101 AND C401.2.
  
 D) EXHAUST VENTILATION CALCULATIONS FOR THE GARAGE -
 SEE TABLE 403.3 AND SECTION 404
  
 4) PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE
 GARAGE- SEE SECTION 404.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  