2017-10-27 11:05:23 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17100767 |
| ADD: 4012 GARDEN AVE. |
| CONT: ABACOA CONSTRUCTION LLC |
| TEL: 561-722-3890 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. OCT. 27/ 2017 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES UNDER THE |
| DESCRIPTION OF WORK REMODEL EXISTING ACCESSORY |
| STRUCTURE. |
| THE SUBMITTED SHEET INDICATES AN EXISTING 20 X 30 FEET |
| EXISTING METAL BUILDING. PLEASE NOTE THE SUBMITTED |
| SURVEY DATED 03-12-15 DOES NOT INDICATE A BUILDING SIZE |
| 20 X 30 FEET. IN MARCH 2015 THE APPLICANT FILED FOR |
| PERMIT (15030114) FOR A 10F X 12F METAL SHED. THIS |
| PERMIT WAS NEVER ISSUED AND REVOKED, SITE VISIT NO WORK |
| COMPLETED AND REVOKED. |
| |
| THE 20F X 30F METAL SHED IS TO BE CONSIDERED NEW WORK |
| SINCE THERE HAS BEEN NO PERMIT PULLED, NO |
| DOCUMENTATION, NO INSPECTIONS. PLEASE ALSO NOTE THE |
| APPLICANT HAS BEEN LICENSED FOR 4 RENTAL UNITS SO THIS |
| REVIEW WILL TAKE PLACE UNDER THE 2014 FBC-BUILDING |
| CODE, NOT THE RESIDENTIAL CODE. |
| |
| 2A) SHEET A-1, DESIGN INFORMATION. THE PROPOSED USE |
| INDICATES OCCUPANCY GROUP R2. THE PLAN SHOWS 2 |
| RESTROOMS, OFFICE AND GARAGE. IT WOULD APPEAR THIS IS A |
| MIXED USE BUILDING BETWEEN BUSINESS AND STORAGE |
| OCCUPANCY SINCE BOTH OCCUPANCY GROUPS ARE OVER 10% OF |
| THE FLOOR AREA. |
| 107.2.1.3. ADDITIONAL DATA REQUIRED. PLEASE DECLARE IF |
| THE GARAGE IS TO BE AN S1 OR S2 USED FOR PARKING |
| VEHICLES. |
| 2014 FBC-B TABLE 508.4 HOUR FIRE RATINGS. |
| FBC-B MIXED USE: 508.1 |
| FBC-B 508.3. NON-SEPARATED OCCUPANCIES |
| FBC-B 508.4 SEPARATED OCCUPANCIES. |
| |
| 2B) SHEET A-1, DESIGN INFORMATION. APPLIED INTERNAL |
| PRESSURE COEFFICIENT IS MARKED N/A, NOT APPLICABLE. |
| PLEASE NOTE FOR EITHER A NEW STRUCTURE OR A SHED THAT |
| WAS DESIGN AS A STORAGE RESIDENTIAL SHED IT IS |
| IMPORTANT IN THE CONSIDERATION OF THE DESIGN. |
| RESIDENTIAL STORAGE SHEDS COULD BE DESIGNED WITH A |
| BUILDING RISK FACTOR I WITH A WIND LOAD/ ZONE |
| REQUIREMENT OF 160 MPH/ VULT WHEREAS WHEN YOU CHANGE |
| THE OCCUPANCY TYPE TO OCCUPIABLE SPACE OR HABITABLE |
| SPACE, BUSINESS OCCUPANCY THE BUILDINGS RISK FACTOR HAS |
| BEEN CHANGED TO II AND WIND ZONE CATEGORY TO 170 VULT |
| MPH. |
| FOR THE ENCLOSED BUILDINGS THE INTERNAL PRESSURE |
| COEFFICIENT IS REQUIRED SINCE IT IS PART OF THE FORMULA |
| OF THE WIND DESIGN CRITERIA FOR PRESSURES BOTH POSITIVE |
| AND NEGATIVE. 2014 FBC-B 1603.1.4(4). |
| |
| 2C) SHEET A-1, DESIGN INFORMATION. THE PLANS INDICATE |
| THIS TO BE A LEVEL II ALTERATION. PLEASE NOTE WE ARE |
| CONSIDERING THIS NEW CONSTRUCTION SINCE NO PERMIT WAS |
| PULLED AND THE SURVEY DATED MARCH 12/2015 DOES NOT SHOW |
| A BUILDING THIS SIZE ON THE SURVEY. UPDATE PLANS. |
| |
| 2D) UNDER THE SCOPE UPDATE TO NEW CONSTRUCTION. |
| |
| 3) WITHIN THE OFFICE THE RESTROOM # 1 IS ONLY 6 FEET IN |
| LENGTH. PLEASE BE AWARE THAT THIS IS CONSIDERED NEW |
| CONSTRUCTION SINCE NO PERMIT WAS PULLED FOR THIS |
| STORAGE UNIT. WILL NEED TO SHOW COMPLIANCE WITH THE |
| 2014 ACCESSIBILITY CODE FIGURE 604.8.1.6 SINGLE USER |
| TOILET ROOMS FOR NEW CONSTRUCTION, ALSO REVIEW 604.3.2. |
| PLEASE NOTE THE PLANS DO NOT SHOW ANY GRAB BARS PER |
| 604.5 FOR THE REAR AND SIDE OF THE WATER CLOSET. PLANS |
| ARE ALSO DEFICIENT IN THE WATER CLOSET HEIGHT SEE |
| 604.4. |
| |
| 4) THE PLANS DO NOT SHOW COMPLIANCE WITH AN ACCESSIBLE |
| ENTRANCE. SUBMITTED WITH THE PLANS IS A PHOTO OF THE |
| SIDE DOOR WHERE HAS A BOTTOM PLATE GOING THROUGH THE |
| BOTTOM OF THE DOOR. PLEASE PROVIDE COMPLIANCE WITH: |
| 2014 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES. |
| (DOORWAYS) |
| IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH |
| 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES |
| SHALL COMPLY WITH 404. BARRIERS AT COMMON OR EMERGENCY |
| ENTRANCES AND EXITS OF BUSINESS ESTABLISHMENTS |
| CONDUCTING BUSINESS WITH THE GENERAL PUBLIC THAT ARE |
| EXISTING, UNDER CONSTRUCTION, OR UNDER CONTRACT FOR |
| CONSTRUCTION WHICH WOULD PREVENT A PERSON FROM USING |
| SUCH ENTRANCES OR EXITS SHALL BE REMOVED. |
| |
| 5) PLEASE PROVIDE COMPLIANCE WITH THE ENERGY CODE |
| SECTIONS: COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF |
| THE FOLLOWING: |
| 5.1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| 5.2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| 5.3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| |
| 6) PLEASE NOTE WE ARE CONSIDERING THIS NEW CONSTRUCTION |
| SINCE NO PERMIT WAS PULLED AND THE SURVEY DATED MARCH |
| 12/2015 DOES NOT SHOW A BUILDING THIS SIZE ON THE |
| SURVEY. PLEASE SUBMIT EITHER A FULL SET OF PLANS |
| INDICATING COMPLIANCE WITH MINIMUM PLAN REVIEW CRITERIA |
| FOR NEW BUILDINGS 107.3.5.1.1 COMMERCIAL BUILDINGS/ |
| BUILDING SECTIONS 1-12 FOR THE BUILDING REVIEW OR IF |
| THE SHED IS A PREMANUFACTURED SHED WITH STATE APPROVAL, |
| SUBMIT THE STATE APPROVED PLANS, WITH APPROVAL NUMBER |
| ON THE PLANS. |
| INCLUSIVE OF (8) |
| ( 8) STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| SOIL CONDITIONS/ANALYSIS |
| TERMITE PROTECTION |
| DESIGN LOADS |
| WIND REQUIREMENTS |
| BUILDING ENVELOPE |
| STRUCTURAL CALCULATIONS (IF REQUIRED) |
| FOUNDATION |
| WALL SYSTEMS |
| FLOOR SYSTEMS |
| ROOF SYSTEMS |
| |
| 7) ADDITIONAL INFORMATION AND CLARIFICATION IS |
| REQUIRED. UNDER THE CITY BUSINESS TAX LICENSE FOR THIS |
| FACILITY IT IS LISTED AS RESIDENTIAL CARE FACILITY, |
| UNDER THE BUSINESS LICENSING THIS IS A GENERIC TERM |
| THAT |
| CAN COVER, ALCOHOL AND DRUG CENTERS, ASSISTED LIVING |
| FACILITIES, CONGREGATE CARE FACILITIES, CONVALESCENT |
| FACILITIES, GROUP HOMES, HALFWAY HOUSES, RESIDENTIAL |
| BOARD AND CUSTODIAL CARE FACILITIES, & SOCIAL |
| REHABILITATION FACILITIES. IF THE OFFICE IS ONE OF THE |
| ABOVE USAGES THE PLANS WILL NEED TO DECLARE THE OFFICE |
| IS PART OF ONE OF THIS TYPE OF FACILITIES, ADDITIONAL |
| COMMENTS MAY APPEAR WHEN DECLARED. |
| |
| 8) PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF |
| THE OTHER BUILDINGS AND THE PROPOSED LOCATION OF THIS |
| STRUCTURE, OCCUPANCY TYPE AND MINIMUM CONSTRUCTION TYPE |
| PLEASE ALSO PROVIDE THE DISTANCES BETWEEN THE |
| STRUCTURES AND THE PROPERTY LINE IN COMPLIANCE WITH |
| TABLE 602 OF THE FBC-B AND TABLE 705.8 FIRE SEPARATION |
| AND ALLOWABLE OPENINGS. |
| |
| 9) SHEET A-1 SHOWS A NEW FRONT FA?ADE BUT THERE IS NO |
| FOUNDATION DESIGN FOR THE ADDITIONAL WEIGHT OR |
| ANCHORING TO THE FOUNDATION TO BE PART OF THE MAIN WIND |
| FORCE RESISTING SYSTEM. 107.3.5.1.1 COMMERCIAL |
| BUILDINGS/ BUILDING SECTION 8 FOUNDATIONS. |
| |
| 10) SHEET A-1 INDICATES THE USE OF EXTERIOR GRADE |
| PLYWOOD AND P. B. METAL LATH. PLEASE REVIEW FBC-B |
| 2510.6 FOR SLIP SHEET PLUS A WATER RESISTANT BARRIER. |
| |
| 11) PLEASE PROVIDE AN EXPLANATION FOR THE LETTER FROM |
| THE DESIGNER OF RECORD JOHN NOSSAL COMMENT # 2 ABOUT |
| THE MODIFICATION OF A WOOD DOOR WHEN WE ALSO HAVE A |
| SUBMITTED PRODUCT APPROVAL FL 12769 FOR A JELD-WEN |
| EXTERIOR DOOR. |
| |
| 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| ON SUBSEQUENT REVIEWS. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |