Plan Review Notes
Plan Review Notes For Permit 17100767
Permit Number 17100767
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-27 11:05:232014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100767
 ADD: 4012 GARDEN AVE.
 CONT: ABACOA CONSTRUCTION LLC
 TEL: 561-722-3890
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. OCT. 27/ 2017
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES UNDER THE
 DESCRIPTION OF WORK REMODEL EXISTING ACCESSORY
 STRUCTURE.
 THE SUBMITTED SHEET INDICATES AN EXISTING 20 X 30 FEET
 EXISTING METAL BUILDING. PLEASE NOTE THE SUBMITTED
 SURVEY DATED 03-12-15 DOES NOT INDICATE A BUILDING SIZE
 20 X 30 FEET. IN MARCH 2015 THE APPLICANT FILED FOR
 PERMIT (15030114) FOR A 10F X 12F METAL SHED. THIS
 PERMIT WAS NEVER ISSUED AND REVOKED, SITE VISIT NO WORK
 COMPLETED AND REVOKED.
  
 THE 20F X 30F METAL SHED IS TO BE CONSIDERED NEW WORK
 SINCE THERE HAS BEEN NO PERMIT PULLED, NO
 DOCUMENTATION, NO INSPECTIONS. PLEASE ALSO NOTE THE
 APPLICANT HAS BEEN LICENSED FOR 4 RENTAL UNITS SO THIS
 REVIEW WILL TAKE PLACE UNDER THE 2014 FBC-BUILDING
 CODE, NOT THE RESIDENTIAL CODE.
  
 2A) SHEET A-1, DESIGN INFORMATION. THE PROPOSED USE
 INDICATES OCCUPANCY GROUP R2. THE PLAN SHOWS 2
 RESTROOMS, OFFICE AND GARAGE. IT WOULD APPEAR THIS IS A
 MIXED USE BUILDING BETWEEN BUSINESS AND STORAGE
 OCCUPANCY SINCE BOTH OCCUPANCY GROUPS ARE OVER 10% OF
 THE FLOOR AREA.
 107.2.1.3. ADDITIONAL DATA REQUIRED. PLEASE DECLARE IF
 THE GARAGE IS TO BE AN S1 OR S2 USED FOR PARKING
 VEHICLES.
 2014 FBC-B TABLE 508.4 HOUR FIRE RATINGS.
 FBC-B MIXED USE: 508.1
 FBC-B 508.3. NON-SEPARATED OCCUPANCIES
 FBC-B 508.4 SEPARATED OCCUPANCIES.
  
 2B) SHEET A-1, DESIGN INFORMATION. APPLIED INTERNAL
 PRESSURE COEFFICIENT IS MARKED N/A, NOT APPLICABLE.
 PLEASE NOTE FOR EITHER A NEW STRUCTURE OR A SHED THAT
 WAS DESIGN AS A STORAGE RESIDENTIAL SHED IT IS
 IMPORTANT IN THE CONSIDERATION OF THE DESIGN.
 RESIDENTIAL STORAGE SHEDS COULD BE DESIGNED WITH A
 BUILDING RISK FACTOR I WITH A WIND LOAD/ ZONE
 REQUIREMENT OF 160 MPH/ VULT WHEREAS WHEN YOU CHANGE
 THE OCCUPANCY TYPE TO OCCUPIABLE SPACE OR HABITABLE
 SPACE, BUSINESS OCCUPANCY THE BUILDINGS RISK FACTOR HAS
 BEEN CHANGED TO II AND WIND ZONE CATEGORY TO 170 VULT
 MPH.
 FOR THE ENCLOSED BUILDINGS THE INTERNAL PRESSURE
 COEFFICIENT IS REQUIRED SINCE IT IS PART OF THE FORMULA
 OF THE WIND DESIGN CRITERIA FOR PRESSURES BOTH POSITIVE
 AND NEGATIVE. 2014 FBC-B 1603.1.4(4).
  
 2C) SHEET A-1, DESIGN INFORMATION. THE PLANS INDICATE
 THIS TO BE A LEVEL II ALTERATION. PLEASE NOTE WE ARE
 CONSIDERING THIS NEW CONSTRUCTION SINCE NO PERMIT WAS
 PULLED AND THE SURVEY DATED MARCH 12/2015 DOES NOT SHOW
 A BUILDING THIS SIZE ON THE SURVEY. UPDATE PLANS.
  
 2D) UNDER THE SCOPE UPDATE TO NEW CONSTRUCTION.
  
 3) WITHIN THE OFFICE THE RESTROOM # 1 IS ONLY 6 FEET IN
 LENGTH. PLEASE BE AWARE THAT THIS IS CONSIDERED NEW
 CONSTRUCTION SINCE NO PERMIT WAS PULLED FOR THIS
 STORAGE UNIT. WILL NEED TO SHOW COMPLIANCE WITH THE
 2014 ACCESSIBILITY CODE FIGURE 604.8.1.6 SINGLE USER
 TOILET ROOMS FOR NEW CONSTRUCTION, ALSO REVIEW 604.3.2.
 PLEASE NOTE THE PLANS DO NOT SHOW ANY GRAB BARS PER
 604.5 FOR THE REAR AND SIDE OF THE WATER CLOSET. PLANS
 ARE ALSO DEFICIENT IN THE WATER CLOSET HEIGHT SEE
 604.4.
  
 4) THE PLANS DO NOT SHOW COMPLIANCE WITH AN ACCESSIBLE
 ENTRANCE. SUBMITTED WITH THE PLANS IS A PHOTO OF THE
 SIDE DOOR WHERE HAS A BOTTOM PLATE GOING THROUGH THE
 BOTTOM OF THE DOOR. PLEASE PROVIDE COMPLIANCE WITH:
 2014 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES.
 (DOORWAYS)
 IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH
 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES
 SHALL COMPLY WITH 404. BARRIERS AT COMMON OR EMERGENCY
 ENTRANCES AND EXITS OF BUSINESS ESTABLISHMENTS
 CONDUCTING BUSINESS WITH THE GENERAL PUBLIC THAT ARE
 EXISTING, UNDER CONSTRUCTION, OR UNDER CONTRACT FOR
 CONSTRUCTION WHICH WOULD PREVENT A PERSON FROM USING
 SUCH ENTRANCES OR EXITS SHALL BE REMOVED.
  
 5) PLEASE PROVIDE COMPLIANCE WITH THE ENERGY CODE
 SECTIONS: COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF
 THE FOLLOWING:
 5.1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 5.2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 5.3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 6) PLEASE NOTE WE ARE CONSIDERING THIS NEW CONSTRUCTION
 SINCE NO PERMIT WAS PULLED AND THE SURVEY DATED MARCH
 12/2015 DOES NOT SHOW A BUILDING THIS SIZE ON THE
 SURVEY. PLEASE SUBMIT EITHER A FULL SET OF PLANS
 INDICATING COMPLIANCE WITH MINIMUM PLAN REVIEW CRITERIA
 FOR NEW BUILDINGS 107.3.5.1.1 COMMERCIAL BUILDINGS/
 BUILDING SECTIONS 1-12 FOR THE BUILDING REVIEW OR IF
 THE SHED IS A PREMANUFACTURED SHED WITH STATE APPROVAL,
 SUBMIT THE STATE APPROVED PLANS, WITH APPROVAL NUMBER
 ON THE PLANS.
 INCLUSIVE OF (8)
 ( 8) STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 FOUNDATION
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
  
 7) ADDITIONAL INFORMATION AND CLARIFICATION IS
 REQUIRED. UNDER THE CITY BUSINESS TAX LICENSE FOR THIS
 FACILITY IT IS LISTED AS RESIDENTIAL CARE FACILITY,
 UNDER THE BUSINESS LICENSING THIS IS A GENERIC TERM
 THAT
 CAN COVER, ALCOHOL AND DRUG CENTERS, ASSISTED LIVING
 FACILITIES, CONGREGATE CARE FACILITIES, CONVALESCENT
 FACILITIES, GROUP HOMES, HALFWAY HOUSES, RESIDENTIAL
 BOARD AND CUSTODIAL CARE FACILITIES, & SOCIAL
 REHABILITATION FACILITIES. IF THE OFFICE IS ONE OF THE
 ABOVE USAGES THE PLANS WILL NEED TO DECLARE THE OFFICE
 IS PART OF ONE OF THIS TYPE OF FACILITIES, ADDITIONAL
 COMMENTS MAY APPEAR WHEN DECLARED.
  
 8) PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF
 THE OTHER BUILDINGS AND THE PROPOSED LOCATION OF THIS
 STRUCTURE, OCCUPANCY TYPE AND MINIMUM CONSTRUCTION TYPE
 PLEASE ALSO PROVIDE THE DISTANCES BETWEEN THE
 STRUCTURES AND THE PROPERTY LINE IN COMPLIANCE WITH
 TABLE 602 OF THE FBC-B AND TABLE 705.8 FIRE SEPARATION
 AND ALLOWABLE OPENINGS.
  
 9) SHEET A-1 SHOWS A NEW FRONT FA?ADE BUT THERE IS NO
 FOUNDATION DESIGN FOR THE ADDITIONAL WEIGHT OR
 ANCHORING TO THE FOUNDATION TO BE PART OF THE MAIN WIND
 FORCE RESISTING SYSTEM. 107.3.5.1.1 COMMERCIAL
 BUILDINGS/ BUILDING SECTION 8 FOUNDATIONS.
  
 10) SHEET A-1 INDICATES THE USE OF EXTERIOR GRADE
 PLYWOOD AND P. B. METAL LATH. PLEASE REVIEW FBC-B
 2510.6 FOR SLIP SHEET PLUS A WATER RESISTANT BARRIER.
  
 11) PLEASE PROVIDE AN EXPLANATION FOR THE LETTER FROM
 THE DESIGNER OF RECORD JOHN NOSSAL COMMENT # 2 ABOUT
 THE MODIFICATION OF A WOOD DOOR WHEN WE ALSO HAVE A
 SUBMITTED PRODUCT APPROVAL FL 12769 FOR A JELD-WEN
 EXTERIOR DOOR.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  