B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-11-06 09:13:25 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. REVISE PLANS TO INCLUDE BUILDING HEIGHT. DESIGN | | PRESSURES APPEAR LOW FOR A HIGH RISE BUILDING. | | | | ALSO CLARIFY CALCULATIONS PREPARED BY MOHAMED W FAHMY, | | PE DATED 8/15/17 WHICH GIVES BUILDING HEIGHT AS 40'. | | BASED ON AERIALS, THIS PARCEL APPEARS TO HAVE ONE | | BUILDING WHICH HAS SEVERAL PORTIONS OF DIFFERENT | | HEIGHTS. IF NECESSARY, PROVIDE NEW CALCULATIONS. | | | | 2. SEOR DID NOT SPECIFY DESIGN PRESSURES FOR THE | | COMPONENTS AND CLADDING. PLEASE CLARIFY; IS THIS | | DELEGATED ENGINEERING? IF YES, THE SEOR IS TO SPECIFY | | THE DESIGN CRITERIA (SUCH AS BUILDING HEIGHT). IF NOT | | DELEGATED ENGINEERING, SEOR IS TO SPECIFY DESIGN | | PRESSURES, FBC B 1609. | | | | | | | | | | | | |
|