2017-10-16 17:15:46RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISE ROOF TILE AERODYNAMIC UPLIFT MOMENT FOR FIELD
 TILE MARKED ON THE FRSA/TRI TABLE 2A SUBMITTED.
 ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS HOUSE
 IS LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED.
 ALSO, PROVIDE TABLE 1A OF FRSA/TRI FOR THE HIP AND
 RIDGE DESIGN PRESSURES FOR FOAM ADHESIVE ON EXPOSURE
 "C".
  
 2- UNDERLAYMENT FLORIDA PRODUCT APPROVAL FL11602-R3
 SUBMITTED: CLEARLY SPECIFY UNDERLAYMENT SYSTEM TO BE
 USED IN FOAM-ON TILE APPLICATION. NOTE: THE MAXIMUM
 DESIGN PRESSURE SHOWN ON-THE FLORIDA PRODUCT APPROVAL
 SUBMITTED DON'T MEET THE DESIGN PRESSURE REQUIRED BY
 SEC. R301.1 FBC-RESIDENTIAL. IF USING THE FRSA/TRI
 TABLES, THEN PROVIDE COPIES OF TABLES THAT APPLY TO THE
 PROPOSED INSTALLATION. IF NOT USING THE FRSA/TRI TABLES
 , THEN PROVIDE ANOTHER PRODUCT APPROVAL THAT MEETS THE
 DESIGN PRESSURE FOR ALL ROOF ZONES.
  