Plan Review Notes For Permit 17100535 |
Permit Number |
17100535 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-10-16 17:15:46 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- REVISE ROOF TILE AERODYNAMIC UPLIFT MOMENT FOR FIELD | | TILE MARKED ON THE FRSA/TRI TABLE 2A SUBMITTED. | | ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS HOUSE | | IS LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED. | | ALSO, PROVIDE TABLE 1A OF FRSA/TRI FOR THE HIP AND | | RIDGE DESIGN PRESSURES FOR FOAM ADHESIVE ON EXPOSURE | | "C". | | | | 2- UNDERLAYMENT FLORIDA PRODUCT APPROVAL FL11602-R3 | | SUBMITTED: CLEARLY SPECIFY UNDERLAYMENT SYSTEM TO BE | | USED IN FOAM-ON TILE APPLICATION. NOTE: THE MAXIMUM | | DESIGN PRESSURE SHOWN ON-THE FLORIDA PRODUCT APPROVAL | | SUBMITTED DON'T MEET THE DESIGN PRESSURE REQUIRED BY | | SEC. R301.1 FBC-RESIDENTIAL. IF USING THE FRSA/TRI | | TABLES, THEN PROVIDE COPIES OF TABLES THAT APPLY TO THE | | PROPOSED INSTALLATION. IF NOT USING THE FRSA/TRI TABLES | | , THEN PROVIDE ANOTHER PRODUCT APPROVAL THAT MEETS THE | | DESIGN PRESSURE FOR ALL ROOF ZONES. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|