2017-11-30 16:03:422ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17100499
 11/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OWNER OR AGENT MUST SIGN AND DATE THE ENERGY
 FORM R405- 2014.
  
 2) THE PLAN SHOWS AN OUTSIDE AIR DUCT FOR THE AC
 SYSTEM. PLEASE PROVIDE THE COMPLIANCE DATA FOR
 MECHANICAL VENTILATION ON PAGE 4 OF ENERGY FORM
 R405-2014.
  
 3) PLEASE SUBMIT THE FLORIDA PRODUCT APPROVAL FOR THE
 BMP CONDENSER TIE-DOWN CLIPS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER