2017-11-17 14:30:101ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE REVISE SHT. A0-41 TO SHOW BATHROOM #4 AS THE
 SPEC B BATH PER FHA DESIGN MANUAL
  
 2. WHEN THE DOOR SWINGS INTO THE USABLE BATHROOM IT IS
 REQUIRED TO HAVE A 30" X 48" CLEAR FLOOR SPACE OUTSIDE
 THE ARC OF THE DOOR SWING, THE LAYOUT FOR BATHROOM #4
 IN UNIT 10D SHOWS THIS CLEAR FLOOR SPACE BEHIND THE
 DOOR WHEN IT IS OPEN WHICH DOES NOT ALLOW A PERSON IN A
 WHEELCHAIR TO ACCESS THIS SPACE IN ORDER TO CLOSE THE
 DOOR I SUGGEST THE DOOR TO SWING OUT INTO THE BEDROOM
 IN ORDER TO COMPLY. PER FHA DESIGN MANUAL PG. 7.39
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  