2017-11-16 15:46:13 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL 2ND REVIEW STATUS: DENIED, SEE COMMENTS |
| BELOW. |
| |
| PREVIOUS COMMENTS NOT ADDRESSED, PROVIDE RESPONSE FOR |
| EACH ITEM: |
| |
| 1. PROVIDE DETAILS OF GFCI RECEPTACLE REQUIRED ON ROOF |
| WITHIN 25 FEET OF CU UNIT. NEC 210.63 |
| 2. PROVIDE DETAILS OF RECEPTACLE CONTROL REQUIRED PER |
| ASHRAE 90.1. THE NOTE SUPPLIED IS NOT ADEQUATE DETAIL, |
| SHOW WHICH CIRCUITS/RECEPTACLES ARE CONTROLLED AND THE |
| METHOD OF CONTROL. THE AREAS INCLUDED SHOULD BE: AT |
| LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP RECEPTACLES IN |
| ALL PRIVATE OFFICES, CONFERENCE ROOMS, ROOMS USED |
| PRIMARILY FOR PRINTING AND/OR COPYING FUNCTIONS, BREAK |
| ROOMS, CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. AT |
| LEAST 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR |
| MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION |
| DOCUMENTS. ASHRAE 90.1, 8.4.2; FBC CE 405.7.1; FBC |
| 107.2.1 |
| 3. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| ETC.. FBC 105.1, 107.2.1 |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |