2017-10-21 12:17:00 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHOW COMPLIANCE WITH THE REAR WALL GRAB BAR SHALL BE |
| 36 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE |
| OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND |
| 24 INCHES MINIMUM ON THE OTHER SIDE. PER FBC ACC |
| 604.5.2 |
| |
| 2. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.1 |
| AND SHALL COMPLY WITH FBC ACC 602 IF ONE IS PROVIDED IN |
| COMMON AREA PLEASE PLACE NOTE ON PLAN. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| |
| 4. A BACKFLOW IS REQUIRED ON THE ICE MAKER LINE. PER |
| FBC PL 608.3 |
| |
| 5. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1 |
| IF ONE IS PROVIDED IN COMMON AREA PLEASE PLACE NOTE ON |
| PLAN. PER WPB AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |