Plan Review Notes
Plan Review Notes For Permit 17100401
Permit Number 17100401
Review Stop P
Sequence Number 1
Notes
Date Text
2017-10-21 12:17:001ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH THE REAR WALL GRAB BAR SHALL BE
 36 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE
 OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND
 24 INCHES MINIMUM ON THE OTHER SIDE. PER FBC ACC
 604.5.2
  
 2. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.1
 AND SHALL COMPLY WITH FBC ACC 602 IF ONE IS PROVIDED IN
 COMMON AREA PLEASE PLACE NOTE ON PLAN. PER WPB AMEND TO
 FBC 107.2.1
  
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 4. A BACKFLOW IS REQUIRED ON THE ICE MAKER LINE. PER
 FBC PL 608.3
  
 5. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
 IF ONE IS PROVIDED IN COMMON AREA PLEASE PLACE NOTE ON
 PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  