Plan Review Notes
Plan Review Notes For Permit 17100401
Permit Number 17100401
Review Stop M
Sequence Number 1
Notes
Date Text
2017-10-26 11:11:101ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING CODE
 PERMIT #17100401
 10/26/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW THE ACTUAL LOCATION OF THE NEW CU-1 ON THE ROOF
 AND PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE STAND AND THE CONDENSER- SECTION 301.15.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  