2017-10-21 10:54:19 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17100401 |
| ADD: 1515 N. FLAGLER DR. SUITE: 800 |
| CONT: LB DEVELOPMENT |
| TEL: 954-709-1926 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. OCT. 21/ 2017 |
| ACTION: DENIED |
| |
| 1) SHEET A-1 THE FLOOR PLAN, THE CORRIDOR WALL IN FRONT |
| OF THE TENANT SPACE HAS MANY WALL IDENTIFICATION TAGS |
| SEE LIST; |
| A- NEW WALL 6 INCHES ABOVE CEILING, NOT RATED |
| C- NEW FIRE RATED WALL SEE SECTION 3/A2 |
| E- NEW WALL TO DECK NOT RATED |
| F- EXISTING CORRIDOR WALL |
| J- MAINTAIN 1 HOUR FIRE RATING 5/8 TYPE X |
| |
| PLEASE CORRECT THE DISCREPANCY IN THE PLANS. THE PAST |
| BUILDING STANDARD WAS A 1 HOUR RATED WALL, OR THE |
| DESIGNER COULD DESIGN TO MAINTAIN THE 1 HOUR FIRE |
| RATING OR NOT. 2014 FBC-B TABLE 1018.1 FIRE SPRINKLERED |
| NOT REQUIRED. DISCREPANCY IN PLANS, 107.2.1.3. |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |