2017-10-21 09:57:062014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100342
 ADD: 2701 OKEECHOBEE BLVD.
 CONT: RJS CONSTRUCTION GROUP
 TEL: 561-795-4712
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. OCT. 21/ 2017
 ORIGINAL STRUCTURE BUILT/ C.O. 1963
 ACTION: DENIED
  
  
 1) PLEASE VIEW THE ADDRESS ON THE SITE PLAN SHEET A1.0,
 IT STATES OKEECHOBEE ROAD WHERE AS THE PERMIT
 APPLICATION STATES 2701 OKEECHOBEE BLVD. AND THE
 CORRESPONDING PROPERTY CONTROL NUMBER
 74-43-43-19-01-000-0022 ALL INDICATE THE OKEECHOBEE
 BLVD LOCATION AS WELL AS THE PALM BEACH COUNTY
 PICTOMETRY OF THE BUILDING AND SITE LOCATION.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK?
  
 2) PLEASE REFER TO SHEET A2.0 THE EXISTING LOFT, PLEASE
 DEFINE THE OCCUPANCY OF THIS AREA, WORK IS SHOWN TO
 OCCUR IN THIS AREA. THE LOFT AREA STILL IS A 2ND STORY
 MID-LEVEL STORY. THERE ARE 2 CODE SECTIONS TO LOOK AT,
 COMMON PATH OF TRAVEL AND AREAS OF STORIES WITH ONLY
 ONE ACCESS TO AN EXIT.
  
 2A) COMMON PATH OF TRAVEL SEE 2014 FBC-B TABLE 1014.3
 FOR BOTH BUSINESS & STORAGE OCCUPANCIES WHEN THE
 OCCUPANT LOAD IS LESS THAN 30/ NON-SPRINKLERED BUILDING
 IS 100 FEET. THE TRAVEL DISTANCE IN THE FURTHEST POINT
 OF THE LOFT AREA IS APPROXIMATELY 148 FEET TO WHERE YOU
 HAVE A CHOICE OF EXITS. THE OTHER ISSUE IS IF THIS
 SPACE IS TO BE DECLARED AS AN OCCUPANCY THEN THE
 OVERALL DIAGONAL DISTANCE (1/2 OF THE OVERALL DIAGONAL
 IS INCREASED FBC-B 1015.2.1.) WHICH YOU DO NOT HAVE ON
 THIS FLOOR. I DO NOT BELIEVE THIS AREA WAS TO BE USED
 EXCEPT FOR EXCESS TO A/C EQUIPMENT, ATTIC SPACE.
  
 2B) UNDER THE FBC-B TABLE 1021.2(2) STORIES WITH ONE
 EXIT OR ACCESS TO ONE EXIT FOR A SECOND FLOOR FOR
 BUSINESS AND STORAGE OCCUPANCIES IT IS LIMITED TO 75
 FEET AND 29 OCCUPANTS, THE 75 FEET IS A MORE
 RESTRICTIVE REQUIREMENT AND BE THE ONE WE WOULD NEED TO
 USE.
  
 3) PLEASE NOTE THIS BUILDING WAS BUILT IN 1963 AND WITH
 AN ELEVATOR SINCE A PORTION OF THE BUILDING IS A 4
 STORY BUILDING. THE VALUE OF THIS PERMIT IS STATED AT
 $105,000.00 DOLLARS. WORK IS CURRENTLY ONLY SHOWING ON
 THE 2ND FLOOR LEVEL BUT THE VIOLATION OCCURS ON FLOORS
 2-4, NO AREA OF REFUGE. THE ACCESSIBILITY CODE
 CAN REQUIRE UP TO 20% OF THE CONTRACT VALUE FOR
 ACCESSIBILITY UPGRADES ($21,000.00) SEE :
  
 2014 FBC-EXISTING BUILDING CODE SECTION 806.1
 ABUILDING, FACILITY OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION AREAS AND
 SEE IN THE EVENT OF DISPROPORTIONALITY.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 ON THE 2ND FLOOR LEVEL THE PLANS DO NOT SHOW AN AREA OF
 REFUGE. THE 2014 ACCESSIBILITY CODE DOES REFER BACK TO
 THE 2003 IBC-B SECTION 1007. 207.1. MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION) (INCORPORATED BY
 REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1).
  
 3A) 2003 IBC-B 1007.6.1. SIZE. EACH AREA OF REFUGE
 SHALL BE SIZED TO ACCOMMODATE ONE WHEEL CHAIR SPACE OF
 30 X 48 INCHES FOR EACH 200 OCCUPANTS.
  
 3B) 2003 IBC-B 1007.6.2. SEPARATION. EACH AREA OF
 REFUGE SHALL BE SEPARATED FROM THE REMAINDER OF THE
 STORY BY A SMOKE BARRIER COMPLYING WITH 709. EACH AREA
 OF REFUGE SHALL BE DESIGNED TO MINIMIZE THE INTRUSION
 OF SMOKE.
  
 3C) 2003 IBC-B 1007.6 .3 TWO-WAY COMMUNICATION. AREAS
 OF REFUGE SHALL BE PROVIDED WITH TWO-WAY COMMUNICATION
 SYSTEM BETWEEN THE AREA OF REFUGE AND A CONTROL POINT.
 IF THE CENTRAL CONTROL POINT IS NOT CONSTANTLY
 ATTENDED, THE AREA OF REFUGE SHALL ALSO HAVE CONTROLLED
 ACCESS TO A PUBLIC TELEPHONE SYSTEM. LOCATION OF THE
 CENTRAL CONTROL POINT SHALL BE APPROVED BY THE FIRE
 DEPARTMENT. TWO-WAY COMMUNICATION SYSTEM SHALL INCLUDE
 BOTH AUDIBLE AND VISIBLE SIGNALS.
  
 3D) 1007.6.4 INSTRUCTIONS. IN AREAS OF REFUGE THAT HAVE
 A TWO-WAY EMERGENCY COMMUNICATIONS SYSTEM, INSTRUCTIONS
 ON THE USE OF THE AREA UNDER EMERGENCY CONDITIONS SHALL
 BE POSTED ADJOINING THE COMMUNICATIONS SYSTEM. THE
 INSTRUCTIONS SHALL INCLUDE ALL OF THE FOLLOWING;
 1) DIRECTIONS TO FIND OTHER MEANS OF EGRESS.
 2) PERSONS ABLE TO USE THE EXIT STAIRWAY DO SO AS SOON
 AS POSSIBLE, UNLESS THEY ARE ASSISTING OTHERS.
 3) INFORMATION ON THE PLANNED AVAILABILITY OF
 ASSISTANCE IN THE USE OF STAIRS OR SUPERVISED OPERATION
 OF ELEVATORS AND HOW TO SUMMON SUCH ASSISTANCE. 4)
 DIRECTIONS FOR THE USE OF THE EMERGENCY COMMUNICATIONS
 SYSTEM.
  
 3E) 1007.6.5 IDENTIFICATION. EACH DOOR PROVIDING ACCESS
 TO AN AREA OF REFUGE FROM AN ADJACENT FLOOR AREA SHALL
 BE IDENTIFIED BY A SIGN COMPLYING WITH ICC A117.,
 STATING AREA OF REFUGE, AND INCLUDING THE INTERNATIONAL
 SYMBOL OF ACCESSIBILITY. WHERE EXIT SIGN ILLUMINATION
 IS REQUIRED BY SECTION 1011.2, THE AREA OF REFUGE SIGN
 SHALL BE ILLUMINATED. ADDITIONALLY, TACTILE SIGNAGE
 COMPLYING WITH ICC A117.1 SHALL BE LOCATED AT EACH DOOR
 TO AN AREA OF REFUGE.
  
 3F) 1007.7. SIGNAGE. AT EXITS AND ELEVATORS SERVING A
 REQUIRED ACCESSIBLE SPACE BUT NOT PROVIDING AN APPROVED
 ACCESSIBLE MEANS OF EGRESS, SIGNAGE SHALL BE INSTALLED
 INDICATING THE LOCATION OF ACCESSIBLE MEANS OF EGRESS.
  
 4) SHEET A2.0. PLEASE ALSO NOTE THIS NEXT CODE
 VIOLATION EXIST ON THE 3RD AND 4TH FLOORS IF THE
 ELEVATOR AND STAIRWAY SHARE THE SAME LANDING AS THE 2ND
 FLOOR CURRENTLY DOES. IN BOTH TODAYS CODE AND THE CODE
 THIS BUILDING WAS BUILT, BUILT IN 1963, UNDER THE 1957
 SOTHERN STANDARD BUILDING CODE THERE WAS REQUIRED
 SEPARATION BETWEEN AN VERTICAL EXIT STAIRWELL AND
 ELEVATOR LANDING. IN THE 1957 STANDARD BUILDING CODE
 SECTION 701.3 STATES ELEVATORS COUNTED AS AN EXIT SHALL
 NOT BE IN THE COMMON ENCLOSING SHAFT WITH A STAIRWAY,
 (WHICH THEY DON?T THEY ARE SEPARATE SHAFTS) AND THE
 PATH OF TRAVEL FROM ONE FLIGHT TO THE NEXT SHALL NOT
 PASS DIRECTLY IN FRONT OF THE ELEVATOR DOORS, WHICH IT
 DOES.
  
 2014 FBC-B 1022.4 OPENINGS. ELEVATORS SHALL NOT OPEN
 INTO INTERIOR EXIT STAIRWAYS AND RAMPS.
 PLEASE REFER TO THE 2014 FBC-EXISTING BUILDING CODE
 SECTION 101.4.2 BUILDINGS PREVIOUSLY OCCUPIED. THE
 LEGAL OCCUPANCY OF ANY BUILDING EXISTING ON THE DATE OF
 ADOPTION OF THIS CODE SHALL BE PERMITTED TO CONTINUE
 WITHOUT CHANGE, EXCEPT AS IS SPECIFICALLY COVERED IN
 THIS CODE, THE FLORIDA FIRE PREVENTION CODE, OR AS IS
 DEEMED NECESSARY BY THE CODE OFFICIAL FOR THE GENERAL
 SAFETY AND WELFARE OF THE OCCUPANTS AND THE PUBLIC.
  
 5) SHEET A2.0 THE 2ND FLOOR ELEVATOR LANDING AND 2ND
 FLOOR STAIRWELL LANDING (SHARED) ALSO HOUSES IN THE
 VERTICAL EXIT, AN EXISTING MAINTENANCE ROOM; IS THIS
 THE ELEVATOR MACHINE ROOM? AGAIN IN TODAYS CODE AS WELL
 AS THE 1957 SSBC YOU CANNOT HAVE EITHER A MAINTENANCE
 ROOM OR ELEVATOR MACHINE ROOM WITH IN THE VERTICAL
 EXIT. UNDER THE 1957 SSBC 701.2 NO OPENINGS SHALL BE
 PERMITTED EXCEPT AS IN SECTION 703.6. IN STAIR
 ENCLOSURE WALLS OR PARTITIONS PROTECTING THE STAIR FROM
 THE INTERIOR OF THE BUILDING, NO OPENINGS EXCEPT THE
 NECESSARY DOORWAYS SHALL BE PERMITTED.
  
 2014 FBC-B 1022.4 OPENINGS. OPENINGS IN INTERIOR EXIT
 STAIRWAYS AND RAMPS OTHER THAN UNPROTECTED EXTERIOR
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT
 ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES
 AND FOR EGRESS FROM THE ENCLOSURE.
 ELEVATORS SHALL NOT OPEN INTO INTERIOR EXIT STAIRWAYS
 AND RAMPS.
  
 PLEASE REFER TO THE 2014 FBC-EXISTING BUILDING CODE
 SECTION 101.4.2 BUILDINGS PREVIOUSLY OCCUPIED. THE
 LEGAL OCCUPANCY OF ANY BUILDING EXISTING ON THE DATE OF
 ADOPTION OF THIS CODE SHALL BE PERMITTED TO CONTINUE
 WITHOUT CHANGE, EXCEPT AS IS SPECIFICALLY COVERED IN
 THIS CODE, THE FLORIDA FIRE PREVENTION CODE, OR AS IS
 DEEMED NECESSARY BY THE CODE OFFICIAL FOR THE GENERAL
 SAFETY AND WELFARE OF THE OCCUPANTS AND THE PUBLIC.
  
 6) SHEET A2.0 THE DOOR SEPARATING THE VERTICAL EXIT
 STAIRWAY, ON THE 2ND FLOOR 4 STORIES, 2 HOUR FIRE
 RATED, INDICATES THEY ARE REMOVING AND REPLACING THE
 3080 TEMPERED GLASS, PLEASE PROVIDE COMPLIANCE WITH
 2014 FBC-B TABLE 716.5 OPENING PROTECTIVES.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 7) SHEET A2.0 IN NOTE 10 INDICATES A NEW 42 INCH HIGH
 RAILING, THE PLAN DOES NOT INDICATE A GUARD RAIL AND NO
 INDICATION OF A HANDRAIL.
  
 7A) THE GUARDRAIL IS INDICTED TO START ON TOP OF THE
 FIRST RISER. PLEASE REFER TO THE 2014 FBC-B 1013.3
 HEIGHT. REQUIRED GUARDS SHALL NOT BE LESS THAN 42
 INCHES HIGH, MEASURED VERTICALLY AS FOLLOWS ;
 (1) FROM THE ADJACENT WALKING SURFACE, THE GUARDRAIL
 SHOULD CONTINUE OUT PAST THE STAIR THE WIDTH OF THE
 STAIR.
  
 7B) THERE IS NO MENTION OF A HANDRAIL, DETAIL ,ETC.?
 FBC-B 012.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT OR RAMP RUN. WHERE HANDRAILS ARE
 NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND
 THE TOP RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF
 ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS WHERE
 HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE
 SAME DIRECTION OF THE STAIR FLIGHTS AT STAIRWAYS AND
 THE RAMP RUNS AT RAMPS.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  