Plan Review Notes For Permit 17100327 |
Permit Number |
17100327 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-03-01 08:56:05 | RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW | | CHECKLIST. | | CODE: FBC 5TH EDITION (2014). | | | | 1- THE VALUE OF THE IMPROVEMENT IS MORE THAN $300.000. | | NEED TO COMPLY WITH THE ROOF TO WALL CONNECTIONS | | ACCORDING TO SEC. 708.8 OF FBC-EXISTING BUILDING CODE, | | 5TH EDITION (2014). SHOW COMPLIANCE. | | | | RESPONSE: REPEAT COMMENT. | | A) NEED TO PROVIDE MORE DETAILED DESCRIPTION OF HOW THE | | CORNERS OF THE BUILDING ARE GOING TO BE STRAPPED. | | CLEARLY IDENTIFY SPECIFIC STRAPS TO BE INSTALLED AND | | NUMBER OF STRAPS AND NAILS PER CORNER TO VERIFY | | COMPLIANCE WITH THE UPLIFT LOADS AS REQUIRED BY SEC. | | 708.8.1 FBC- EXISTING BUILDING. PROVIDE COMPLETE SKETCH | | SHOWING PROPOSED STRAPPING ON EACH CORNER OF THIS | | BUILDING. SEC. 107.2.1 CITY AMENDMENTS. | | NOTE: ESTIMATED VALUE TO STRAP EACH CORNER SEEMS TO BE | | HIGH. PROVIDE A DETAILED BREAKDOWN OF THE SCOPE OF WORK | | REQUIRED TO PROVIDE THE ROOF TO WALL CONNECTIONS TO | | JUSTIFY THE ESTIMATED VALUE OF $1000 PER CORNER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|