Date |
Text |
2018-01-09 15:49:17 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| ORIGINAL COMMENT: |
| 1- THE VALUE OF THE IMPROVEMENT IS MORE THAN $300.000. |
| NEED TO COMPLY WITH THE ROOF TO WALL CONNECTIONS |
| ACCORDING TO SEC. 708.8 OF FBC-EXISTING BUILDING CODE, |
| 5TH EDITION (2014). SHOW COMPLIANCE. |
| |
| RESPONSE: |
| A) THE COST ESTIMATE LETTER FROM HORIZON CUSTOM BUILDER |
| INC. TO PROVIDE ROOF TO WALL CONNECTIONS IS INCORRECT. |
| THE LETTER IS REFERENCING A BUILDING WITH 12 CORNERS. |
| THERE ARE TWO BUILDINGS IN THIS PROPERTY. THE ROOFING |
| PERMIT APPLICATION IS FOR THE REAR BUILDING AND IT |
| DOESN'T HAVE 12 CORNERS. REVISE LETTER AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) NEED TO PROVIDE MORE DETAILED DESCRIPTION OF HOW THE |
| FOUR CORNERS OF THE BUILDING ARE GOING TO BE STRAPPED. |
| CLEARLY IDENTIFY SPECIFIC STRAP TO BE INSTALLED AND |
| NUMBER OF STRAPS AND NAILS PER CORNER. NOTE: ACCORDING |
| TO FIGURE R301.2(7) CORNERS ARE 4'-0" X 4'-0" MINIMUM. |
| SEC. R301.1 FBC-RESIDENTIAL. |
| |
| C) LETTER SUBMITTED DOESN'T HAVE ANY SIGNATURE. THE |
| LETTER NEEDS TO BE SIGNED BY THE PERSON RESPONSIBLE FOR |
| THE ESTIMATE. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| |