Plan Review Notes
Plan Review Notes For Permit 17100327
Permit Number 17100327
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-16 09:54:32RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- THE VALUE OF THE IMPROVEMENT IS MORE THAN $300.000.
 NEED TO COMPLY WITH THE ROOF TO WALL CONNECTIONS
 ACCORDING TO SEC. 708.8 OF FBC-EXISTING BUILDING CODE,
 5TH EDITION (2014). SHOW COMPLIANCE.
  
 2- INFORMATION MARKED ON THE PACKAGE SUBMITTED IS
 INCORRECT. ACCORDING TO SEC. R301.2.1.4 FBC
 FBC-RESIDENTIAL, 5TH EDITION (2014) THIS HOUSE IS
 LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED.
  
 3- PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO FLORIDA PRODUCT APPROVAL FL16709-R3
 SUBMITTED. AND PROVIDE THE INSTALLATION INSTRUCTIONS
 THAT COMES WITH THIS PRODUCT APPROVAL. GO TO THE
 FLORIDA PRODUCT APPROVAL WEBSITE AND DOWNLOAD
 CORRESPONDING INFORMATION. NOTE: FLORIDA PRODUCT
 APPROVAL COVER PAGE SPECIFIES IF THE PRODUCT IS
 APPROVED AND THE CURRENT CODE. THAT'S WHY THIS COVER
 PAGE IS REQUIRED ALSO.
 FAC 61G20-3.001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]