Plan Review Notes For Permit 17100310 |
Permit Number |
17100310 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-10-24 10:43:29 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17100310 | | MASTER #16120590 | | 10/24/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SIGNATURE OF CONTRACTOR OR QUALIFIER ON PLANS | | REQUIRED: SEE FLORIDA STATUTE 633.021, AND SECTION | | 107.2.1 FBC. WPB AMENDMENTS TO THE FBC: ALL | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN. | | | | 2) PROVIDE A FUEL PIPING DIAGRAM. | | | | 3) SUBMIT MANUFACTURER'S PRODUCT SHEETS THAT PROVIDE | | LISTING AND LABELING INFORMATION FOR THE FUEL TANK- | | SECTION 21.4.2.1.1 NFPA 30-2015. | | | | 4) SUBMIT MANUFACTURER'S PRODUCT SHEETS THAT PROVIDE | | LISTING AND LABELING INFORMATION FOR THE FUEL LINES- | | SECTION 27.4.1 NFPA 30-2015. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|