2018-03-23 18:46:07 | APPROVED WITH EXCEPTIONS |
| BUILDING PROVISO |
| |
| 1) THE PERMIT (#06050833) FOR THE ADDITION TO THE REAR |
| OF THE STRUCTURE EXPIRED PRIOR TO RECEIVING ALL OF THE |
| REQUIRED INSPECTIONS. PLEASE BE ADVISED THE INSPECTOR |
| MAY REQUIRE PREVIOUSLY COMPLETED WORK TO BE MADE |
| ACCESSIBLE AND OPEN FOR INSPECTION OR REQUIRE |
| ADDITIONAL DOCUMENTATION FOR ALL CONCEALED WORK |
| PREVIOUSLY COMPLETED PURSUANT TO FBC 110 & FBC 117. |
| FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A |
| PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY |
| THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK |
| SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION |
| PURPOSES UNTIL APPROVED. |
| FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| |
| 2) A SET OF THE APPROVED PLANS FROM THE EXPIRED PERMIT |
| (#06050833) HAS BEEN PROVIDED FOR REFERENCE AND TO AID |
| THE INSPECTORS WITH THEIR FIELD INSPECTIONS. FBC |
| 107.2.1.3 |
| |
| 3) A SET OF THE APPROVED PRODUCT APPROVALS FROM THE |
| EXPIRED PERMIT (#06050833) HAS BEEN PROVIDED FOR |
| REFERENCE AND TO AID THE INSPECTORS WITH THEIR FIELD |
| INSPECTIONS. FBC 107.2.1.3 THE RECORDS INDICATE THAT |
| THE FOLLOWING STRUCTURAL INSPECTIONS WERE APPROVED: 114 |
| - SLAB, 105 - FOOTING, 120 - BEAM/COLUMN, 111 - ROOF |
| FRAMING, 118 - ROOF SHEATHING, AND A 119 WINDOW/DOOR |
| BUCK. SEE ATTACHED COPY OF INSPECTION RESULTS FROM |
| EXPIRED PERMIT (#06050833). |
| |
| 4) OWNER/AGENT TO SIGN AND DATE ENERGY FORM. |
| |
| 5) SUBMIT TWO SETS OF INSTALLATION INSTRUCTION FOR THE |
| TAMKO ASPHALT SINGLES. |
| |
| |
| |
| |
| |
| |