2018-01-08 18:38:50PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 2) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR
 R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE
 FORMS AS REQUIRED.
  
 3) SPECIFY THE MODEL NUMBERS AND SPECIFICATIONS FOR THE
 HEATING AND COOLING EQUIPMENT, THAT MATCHES THE
 EQUIPMENT SIZING CALCULATIONS, ON THE PLANS. AIR
 HANDLER INFORMATION IS MISSING. PROVIDE AHRI
 CERTIFICATIONS FOR THE EQUIPMENT. FBC-R M1401.3
  
 4) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  