Plan Review Notes For Permit 17100279 |
Permit Number |
17100279 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-01-05 07:39:35 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS: | | 1. CORRECTED. | | 2. CORRECTED. | | 3. CORRECTED. | | 4. CORRECTED. | | 5. CORRECTED. | | 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | SERVICE. NEC 250.94; FBC RE3609.3 (NOT SHOWN ON PLAN.) | | 7. CORRECTED. | | | | NEW COMMENT: | | 8. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED | | TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON | | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC | | 107.2.1, FS 471, 481, 481.229 | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|