2017-10-23 15:42:1410/23/17 1ST PLUMBING REVIEW DENIED
  
 1) VALUE SEEMS LOW AND APPREARS TO HAVE BEEN CHANGED
 AFTER QUALIFIER FILL OUT APPLICATION. PROVIDE BONA FIDE
 SIGED CONTRACT FBC 109.3
  
 2) PROVIDE SANITARY ISOMETRIC DRAWNING OF THE PLUMBING
 SYSTEM FBC 107.2.1
  
 3) SHOW SIZING AND SOURCE OF HOT WATER FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER