2017-10-31 08:15:02 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. BLOCK NOTE STATES THAT RECEPTACLES SHALL BE TAMPER |
| RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| CORRECTION. NEC 406.12; FBC RE4002.14 |
| 2. SHOW ALL SMOKE AND CO ALARMS IN HOUSE. PLAN |
| CURRENTLY ONLY SHOWS NEW AREA FOR THESE ALARMS. IF NONE |
| ARE EXISTING, OR NOT TO CODE, PROVIDE AS NEW |
| INSTALLATION. FBC R314.3, FBC 107.2.1 |
| 3. PANEL SCHEDULE SHOWS TWO AHU'S AT 10KW EACH, BUT THE |
| LOAD CALCULATION SHOWS ONE AT 10 KW AND ONE AT 1 KW. |
| PROVIDE CORRECTED LOAD CALCULATION. NEC 220; FBC |
| RE3602.3 |
| 4. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC |
| 410.10(D); FBC RE4003.11 |
| 5. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED |
| LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT |
| BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. |
| NEC 410.16; FBC RE4003.12 |
| 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. NEC 250.94; FBC RE3609.3 |
| 7. FOR AHU INSTALLED IN ATTIC, CODE REQUIRES: "A |
| LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE |
| REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET |
| SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN |
| ACCORDANCE WITH CHAPTER 34." PROVIDE RECEPTACLE OUTLET |
| PER CODE. FBC-RE M1305.1.3.1 |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |