2017-11-03 18:32:21 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PERMIT (#06050833) FOR THE ADDITION TO THE REAR |
| OF THE STRUCTURE EXPIRED PRIOR TO RECEIVING ALL OF THE |
| REQUIRED INSPECTIONS. |
| PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY |
| COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR |
| INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL |
| CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110 |
| & FBC 117. |
| FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A |
| PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY |
| THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK |
| SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION |
| PURPOSES UNTIL APPROVED. |
| FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| |
| 2) OBTAIN A SET OF THE APPROVED PLANS THAT EXPIRED |
| (PERMIT #06050833) AND SUBMIT THEM WITH THE NEW PLANS |
| FOR REFERENCE AND TO AID THE INSPECTORS WITH THEIR |
| FIELD INSPECTIONS. FBC 107.2.1.3 (CONTACT CRAIG |
| MCPHERSON AT 561-805-6684 OR [email protected] TO |
| OBTAIN COPIES FROM OUR FILES.) |
| |
| 3) SUBMIT A SET OF THE APPROVED PRODUCT APPROVALS FOR |
| THE EXPIRED PERMIT AND SUBMIT THEM FOR REFERENCE AND TO |
| AID THE INSPECTORS WITH THEIR FIELD INSPECTIONS. FBC |
| 107.2.1.3 |
| |
| 4) SPECIFY THE ATTACHEMENT OF THE 4 X 6 WOOD POSTS TO |
| THE GLULAM BEAM IN THE DETAIL ON 4.1. FBC-R 301.1 |
| |
| 5) THE NOTES FOR THE UPTURN BEAM ON SHEETS 2.1 AND 3.1 |
| STATE, "SEE DETAIL THIS SHEET.". THERE IS NO DETAIL FOR |
| THE UPTURN BEAM ON THESE SHEETS. PLEASE CORRECT. FBC |
| 107.2.1 |
| |
| 6) REVISE THE TYPICAL WALL SECTION ON SHEET 4.1 TO |
| SPECIFY 8D RING SHANK NAILS PER FBC-R 803.2.3.1. |
| |
| 7) REVISE THE TYPICAL WALL SECTION ON SHEET 4.1 TO |
| SPECIFY A DOUBLE LAYER OF UNDERLAYMENT AS REQUIRED BY |
| FBC-R 905.2.2 FOR ROOF SLOPES LESS THAN 4:12. |
| |
| 8) SHOW COMPLIANCE WITH FBC-R 314.3.1 WHEN ALTERATIONS, |
| REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN |
| ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN |
| EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL |
| BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR |
| NEW DWELLINGS. |
| |
| |
| |
| |
| |