Plan Review Notes
Plan Review Notes For Permit 17100279
Permit Number 17100279
Review Stop B
Sequence Number 1
Notes
Date Text
2017-11-03 18:32:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PERMIT (#06050833) FOR THE ADDITION TO THE REAR
 OF THE STRUCTURE EXPIRED PRIOR TO RECEIVING ALL OF THE
 REQUIRED INSPECTIONS.
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 2) OBTAIN A SET OF THE APPROVED PLANS THAT EXPIRED
 (PERMIT #06050833) AND SUBMIT THEM WITH THE NEW PLANS
 FOR REFERENCE AND TO AID THE INSPECTORS WITH THEIR
 FIELD INSPECTIONS. FBC 107.2.1.3 (CONTACT CRAIG
 MCPHERSON AT 561-805-6684 OR [email protected] TO
 OBTAIN COPIES FROM OUR FILES.)
  
 3) SUBMIT A SET OF THE APPROVED PRODUCT APPROVALS FOR
 THE EXPIRED PERMIT AND SUBMIT THEM FOR REFERENCE AND TO
 AID THE INSPECTORS WITH THEIR FIELD INSPECTIONS. FBC
 107.2.1.3
  
 4) SPECIFY THE ATTACHEMENT OF THE 4 X 6 WOOD POSTS TO
 THE GLULAM BEAM IN THE DETAIL ON 4.1. FBC-R 301.1
  
 5) THE NOTES FOR THE UPTURN BEAM ON SHEETS 2.1 AND 3.1
 STATE, "SEE DETAIL THIS SHEET.". THERE IS NO DETAIL FOR
 THE UPTURN BEAM ON THESE SHEETS. PLEASE CORRECT. FBC
 107.2.1
  
 6) REVISE THE TYPICAL WALL SECTION ON SHEET 4.1 TO
 SPECIFY 8D RING SHANK NAILS PER FBC-R 803.2.3.1.
  
 7) REVISE THE TYPICAL WALL SECTION ON SHEET 4.1 TO
 SPECIFY A DOUBLE LAYER OF UNDERLAYMENT AS REQUIRED BY
 FBC-R 905.2.2 FOR ROOF SLOPES LESS THAN 4:12.
  
 8) SHOW COMPLIANCE WITH FBC-R 314.3.1 WHEN ALTERATIONS,
 REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS.
  
  
  
  
  