Plan Review Notes For Permit 17100262 |
Permit Number |
17100262 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-10-12 12:20:24 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL, ENERGY | | CONSERVATION CODES | | PERMIT #17100262 | | 10/12/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) ENERGY CONSERVATION COMPLIANCE IS REQUIRED IN | | ACCORDANCE WITH SECTION R101.4.5 CHANGE IN SPACE | | CONDITIONING.: | | ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME | | CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO | | FULL COMPLIANCE WITH THIS CODE. PLEASE SEE SECTION | | TABLE R101.5.1 AND SUBMIT A COMPLIANCE REPORT. | | | | 2) THE TRANSFER DUCT FROM THE MASTER BEDROOM IS | | UNDERSIZED PER SECTION M1602.4 EXCEPTION 1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|