2017-10-12 12:20:241ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL, ENERGY
 CONSERVATION CODES
 PERMIT #17100262
 10/12/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENERGY CONSERVATION COMPLIANCE IS REQUIRED IN
 ACCORDANCE WITH SECTION R101.4.5 CHANGE IN SPACE
 CONDITIONING.:
 ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME
 CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO
 FULL COMPLIANCE WITH THIS CODE. PLEASE SEE SECTION
 TABLE R101.5.1 AND SUBMIT A COMPLIANCE REPORT.
  
 2) THE TRANSFER DUCT FROM THE MASTER BEDROOM IS
 UNDERSIZED PER SECTION M1602.4 EXCEPTION 1.
  