Plan Review Notes For Permit 17100244 |
Permit Number |
17100244 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-01-11 15:53:22 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) THERE ARE NO RACK/RACK SYSTEM INDICATED. IF RACKS | | ARE GOING TO BE INSTALLED THEY SHALL BE SUBMITTED UNDER | | SEPARATE SHOPE DRAWINGS. | | | | PER NFPA 1, CHAPTER 34, GENERAL STORAGE. | | | | 34.7.3 STORAGE ARRANGEMENT. | | 34.7.3.1* RACK STRUCTURE. RACK CONFIGURATIONS SHALL BE | | APPROVED. | | 34.7.3.2* RACK LOADING. RACKS SHALL NOT BE LOADED | | BEYOND THEIR DESIGN CAPACITY. | | | | PLEASE INCLUDE SPEC SHEETS AND TYPE OF COMMODITY AND | | HOW IT WILL BE PALLETIZED WITH THE SEPARATE SUBMITTAL. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | |
|