Date |
Text |
2018-01-23 09:30:58 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17100244 |
| ADD: 1125 OKEECHOBEE RD. |
| CONT: ALL PURPOSE CONSTRUCTION |
| TEL: 561-507-5448 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: 2ND REVIEW |
| ACTION: DENIED |
| |
| 1A-D) COMPLIED. |
| |
| 2A-D) COMPLIED. |
| |
| 3A-B) COMPLIED. |
| |
| 4) 2ND REQUEST. SUBMITTED SOILS REPORTS ARE COPIED |
| SIGNED AND SEALED SIGNATURES. 61G15-23.002(2) FL. |
| ADMIN. CODE. |
| |
| 5) SEMI-COMPLIED. SHEET S-1 ONLY GIVE THE WALL |
| PRESSURES FOR ZONES 4 & 5 NO ROOF PRESSURES FOR ROOF |
| ZONES 1-3. PLEASE NOTE ONLY A 2 FOOT PARAPET SO THERE |
| IS A ROOF ZONE 3. PLEASE PROVIDE THE ROOF PRESSURES FOR |
| ZONES 1-3, IN VASD. THANK YOU. 2014 FBC-B 1603.1.4 WIND |
| DESIGN DATA. |
| |
| 6A) 2ND REQUEST. PLEASE NOTE THE FLORIDA APPROVAL FL |
| 13624-R6 ONLY ONE COVERSHEET SUBMITTED, NO TECHNICAL |
| SHEETS ATTACHED. WILL NEED 2 COMPLETE SETS OF THE |
| PRODUCT APPROVAL, AND REVIEWED BY THE DESIGN |
| PROFESSIONAL. |
| |
| 6B) THE MIAMI-DADE NOA 14-0331.02 FOR DHS-500 ALUMINUM |
| STOREFRONT SYSTEM IS FOR THE WINDOWS ONLY NOT FOR THE |
| DOOR, THAT IS A DIFFERENT PRODUCT APPROVAL. |
| |
| 6C) IN REVIEWING THE WINDOW PRODUCT APPROVAL I FOUND A |
| DISCREPANCY IN THE PLANS. SHEET A201 SHOWS THE FRONT |
| DOOR IDENTIFIED AS UNIT 101. SHEET A-203 IN THE DOOR |
| SCHEDULE INDICATES THE DOOR TO BE A 7-0 FOOT TALL DOOR. |
| SHEET A301 THE FRONT ELEVATION SHOWS A 8 FOOT TALL DOOR |
| AND WINDOW SYSTEM. DISCREPANCY IN PLANS. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. PRESSURES GOOD FOR |
| STOREFRONT WINDOW. |
| |
| 6D) THE ROOFING PRODUCT APPROVALS SUBMITTED CODE NOT BE |
| REVIEWED SINCE THERE IS NO CHART PROVIDING THE POSITIVE |
| AND NEGATIVE PRESSURES. 2014 FBC-B 1603.1.4 WIND DESIGN |
| DATA |
| |
| 6E) THE SUBMITTED MIAMI-DADE NOA 15-1008.01 A GAF |
| RUBEROID MODIFIED BITUMEN FOR STEEL DECKS, A 91 PAGE |
| REPORT. NO SUB-SYSTEM HAS BEEN IDENTIFIED, WILL NEED |
| SUB-SYSTEM IDENTIFIED AND ASSOCIATED PRESSURES AND |
| LIMITATIONS EITHER 7 OR 9. |
| 6F) THE SUBMITTED MIAMI-DADE NOA 15-0129.16 PLEASE |
| REVIEW SHEET 4 OF 5 AND IDENTIFY THE SUB-SYSTEM TO BE |
| APPLIED. SHEET 5 0F 5 REVIEW LIMITATIONS. |
| |
| 7) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. |
| PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 8 )COMPLIED. |
| |
| 9) PROVISO: SHEET S-3 SHOW METAL DECKING AND BAR JOIST. |
| PLEASE PROVIDE COMPLIANCE WITH WELDING CERTIFICATE FOR |
| INSPECTOR AT JOBSITE. THE CONTRACTOR IS REQUIRED TO |
| PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| THE REFERENCED STANDARDS AT TIME OF INSPECTION. |
| 2014 FBC-B 2204.1 WELDING |
| 2014 FBC-B 2204.2 BOLTING. |
| |
| 10-14) COMPLIED. |
| |
| 15) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE |
| CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY |
| IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS |
| 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF |
| PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE |
| PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE |
| CALL (561)233-5025 FOR MORE INFORMATION. |
| |
| 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |