2017-11-04 11:44:42 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. A-202 DETAIL #1 IT APPEARS THE CLEAR FLOOR |
| SPACE FOR THE FIXTURES IS BEING SHOWN OUTSIDE THE |
| BATHROOM. PLEASE SHOW THE FIXTURES INSIDE THE REQUIRED |
| CLEAR FLOOR SPACE AND PROVIDE DIMENSIONS ON FLOOR |
| SPACE. PER WPB AMEND TO FBC 107.2.1 |
| |
| 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 |
| DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS |
| DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW. |
| |
| 3. SHT. A-202 DETAIL #3 THE WATER CLOSET DIMENSION OFF |
| THE SIDE WALL SHALL BE 16" MIN. AND 18" MAX. PER FBC |
| ACC 604.2 |
| |
| 4. A-201 UNDER APPLICABLE CODE IT LIST THE EXISTING |
| BUILDING CODE AND CHANGE OF USE THE PLAN CALLS IT A NEW |
| WAREHOUSE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 5. SHT. A-401 THE ROOF DRAIN CALCULATIONS LIST A MAIN |
| HOUSE AND GUEST HOUSE WITH DIFFERENT SQFT THAN THE ROOF |
| PLAN SHOWS PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 6. THE PERMIT APPLICATION SHOWS UNDER WORK DESCRIPTION |
| A NEW SFR PLEASE CLARIFY AND CORRECT APPLICATION. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 7. SHT. A-401 THE ROOF DRAIN ISOMETRIC SHOWS THE |
| HORIZONTAL PIPING RUN AT 1/8" PER FT PER TABLE 1106.3 |
| 4" AT 1/8" PER FT IS 1800 SQFT MAX . THE LAST SECTION |
| OF HORIZONTAL PIPING SHALL BE 5" MIN OR RUN AT 1/4" PER |
| FT PLEASE CORRECT PLAN PER FBC PL TABLE 1106.3 |
| |
| 8. SHT. A-402 PROVIDE DETAIL THAT SHOWS THE DIMENSIONS |
| OF THE OVERFLOW SCUPPER SIZED PER FBC PL TABLE 1106.7 |
| |
| 9. A SEPARATE PERMIT IS REQUIRED FOR BACKFLOW PER WPB |
| UTILITIES DEPT. PLEASE PROVIDE NOTE ON PLAN. |
| |
| 10. PLEASE SHOW COMPLIANCE WITH FBC PL 416.5 TEMPERED |
| WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. |
| |
| 11. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1 |
| |
| 12. HOT WATER IS REQUIRED AT SERVICE SINK PER FBC PL |
| 607.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |