Plan Review Notes
Plan Review Notes For Permit 17100244
Permit Number 17100244
Review Stop P
Sequence Number 1
Notes
Date Text
2017-11-04 11:44:421ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-202 DETAIL #1 IT APPEARS THE CLEAR FLOOR
 SPACE FOR THE FIXTURES IS BEING SHOWN OUTSIDE THE
 BATHROOM. PLEASE SHOW THE FIXTURES INSIDE THE REQUIRED
 CLEAR FLOOR SPACE AND PROVIDE DIMENSIONS ON FLOOR
 SPACE. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
  
 3. SHT. A-202 DETAIL #3 THE WATER CLOSET DIMENSION OFF
 THE SIDE WALL SHALL BE 16" MIN. AND 18" MAX. PER FBC
 ACC 604.2
  
 4. A-201 UNDER APPLICABLE CODE IT LIST THE EXISTING
 BUILDING CODE AND CHANGE OF USE THE PLAN CALLS IT A NEW
 WAREHOUSE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. A-401 THE ROOF DRAIN CALCULATIONS LIST A MAIN
 HOUSE AND GUEST HOUSE WITH DIFFERENT SQFT THAN THE ROOF
 PLAN SHOWS PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 6. THE PERMIT APPLICATION SHOWS UNDER WORK DESCRIPTION
 A NEW SFR PLEASE CLARIFY AND CORRECT APPLICATION. PER
 WPB AMEND TO FBC 107.2.1
  
 7. SHT. A-401 THE ROOF DRAIN ISOMETRIC SHOWS THE
 HORIZONTAL PIPING RUN AT 1/8" PER FT PER TABLE 1106.3
 4" AT 1/8" PER FT IS 1800 SQFT MAX . THE LAST SECTION
 OF HORIZONTAL PIPING SHALL BE 5" MIN OR RUN AT 1/4" PER
 FT PLEASE CORRECT PLAN PER FBC PL TABLE 1106.3
  
 8. SHT. A-402 PROVIDE DETAIL THAT SHOWS THE DIMENSIONS
 OF THE OVERFLOW SCUPPER SIZED PER FBC PL TABLE 1106.7
  
 9. A SEPARATE PERMIT IS REQUIRED FOR BACKFLOW PER WPB
 UTILITIES DEPT. PLEASE PROVIDE NOTE ON PLAN.
  
 10. PLEASE SHOW COMPLIANCE WITH FBC PL 416.5 TEMPERED
 WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 11. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 12. HOT WATER IS REQUIRED AT SERVICE SINK PER FBC PL
 607.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  