2017-11-07 10:12:35 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17100244 |
| 11/7/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| PLEASE ADDRESS THE FOLLOWING COMMENTS. |
| |
| 1) SHEET A-201: REFER TO BUILDING REVIEW COMMENTS AND |
| ADDRESS THE DISCREPANCIES IN THE BUILDING CODE AND |
| DESIGN ANALYSIS. THE DESCRIPTION OF WORK IS INDICATING |
| A NEW RESTAURANT TO BE BUILT-OUT IN A VACANT SPACE, |
| HOWEVER THIS IS A NEW BUILDING THAT YOU ARE CLASSIFYING |
| AS A STORAGE/WAREHOUSE. A THOROUGH MECHANICAL REVIEW |
| CANNOT BE COMPLETED AT THIS TIME. |
| |
| 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| 5-TON AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY |
| CONSERVATION AND SECTION 312.1 FBC-14 MECHANICAL. |
| |
| 3) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH |
| THE FBC-14 ENERGY CONSERVATION CODE. REFER TO SECTIONS |
| C101.5 AND C401.2 AND SUBMIT AN ENERGY COMPLIANCE |
| REPORT. |
| |
| 4) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. |
| PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDED CFMS OF OUTDOOR AIR. |
| |
| 5) INDICATE HOW OUTDOOR AIR IS BEING PROVIDED TO THE |
| NEW AIR HANDLER, AND COMPLY WITH SECTION C403.2.4.4. |
| FOR REQUIRED DAMPER. |
| |
| 6) SHEETS A-501 & A-502: KEY NOTE #1 NOT SHOWN ON THE |
| PLAN. PLEASE SHOW THE CONDENSATE PIPING RUN AND |
| DISPOSAL LOCATION. |
| |
| 7) A-501 & A-502: A SMOKE DETECTOR IS REQUIRED IN THE |
| RETURN AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION |
| 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED |
| IF THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS |
| ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY |
| AIR, HOWEVER HE PLAN IS INDICATING 2320 CFMS OF SUPPLY |
| AIR. |
| |
| 8) A-501 & A-502: PROVIDE AN AIR DEVICE SCHEDULE TO |
| MATCH THE SYMBOLS ON THE PLAN. |
| |
| 9) A-501 & A-502: SHOW THE BATH EXHAUST DUCT RUN AND |
| TERMINATION LOCATION AND A TERMINATION CAP DETAIL. |
| |
| 9) ADVISORY: A NON-COMBUSTIBLE DOOR FOR THE AC CLOSET |
| WILL BE REQUIRED IF THE RETURN IS NOT DUCTED DIRECTLY |
| TO THE AIR HANDLER- SEE SECTION C403.2.7.2 FBC-14 |
| ENERGY CONSERVATION CODE, AND SECTION 602.2.1 FBC-14 |
| MECHANICAL. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
| |