2017-11-07 10:12:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100244
 11/7/17
  
 PLAN REVIEW RESULTS: DENIED.
 PLEASE ADDRESS THE FOLLOWING COMMENTS.
  
 1) SHEET A-201: REFER TO BUILDING REVIEW COMMENTS AND
 ADDRESS THE DISCREPANCIES IN THE BUILDING CODE AND
 DESIGN ANALYSIS. THE DESCRIPTION OF WORK IS INDICATING
 A NEW RESTAURANT TO BE BUILT-OUT IN A VACANT SPACE,
 HOWEVER THIS IS A NEW BUILDING THAT YOU ARE CLASSIFYING
 AS A STORAGE/WAREHOUSE. A THOROUGH MECHANICAL REVIEW
 CANNOT BE COMPLETED AT THIS TIME.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 5-TON AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION AND SECTION 312.1 FBC-14 MECHANICAL.
  
 3) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH
 THE FBC-14 ENERGY CONSERVATION CODE. REFER TO SECTIONS
 C101.5 AND C401.2 AND SUBMIT AN ENERGY COMPLIANCE
 REPORT.
  
 4) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 5) INDICATE HOW OUTDOOR AIR IS BEING PROVIDED TO THE
 NEW AIR HANDLER, AND COMPLY WITH SECTION C403.2.4.4.
 FOR REQUIRED DAMPER.
  
 6) SHEETS A-501 & A-502: KEY NOTE #1 NOT SHOWN ON THE
 PLAN. PLEASE SHOW THE CONDENSATE PIPING RUN AND
 DISPOSAL LOCATION.
  
 7) A-501 & A-502: A SMOKE DETECTOR IS REQUIRED IN THE
 RETURN AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS
 ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY
 AIR, HOWEVER HE PLAN IS INDICATING 2320 CFMS OF SUPPLY
 AIR.
  
 8) A-501 & A-502: PROVIDE AN AIR DEVICE SCHEDULE TO
 MATCH THE SYMBOLS ON THE PLAN.
  
 9) A-501 & A-502: SHOW THE BATH EXHAUST DUCT RUN AND
 TERMINATION LOCATION AND A TERMINATION CAP DETAIL.
  
 9) ADVISORY: A NON-COMBUSTIBLE DOOR FOR THE AC CLOSET
 WILL BE REQUIRED IF THE RETURN IS NOT DUCTED DIRECTLY
 TO THE AIR HANDLER- SEE SECTION C403.2.7.2 FBC-14
 ENERGY CONSERVATION CODE, AND SECTION 602.2.1 FBC-14
 MECHANICAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  