Plan Review Notes
Plan Review Notes For Permit 17100242
Permit Number 17100242
Review Stop B
Sequence Number 2
Notes
Date Text
2017-10-26 07:10:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE SUBMITTAL INCLUDES SHOP DRAWINGS WHICH ARE NOT
 DELEGATED ENGINEERING. PLEASE REMOVE FROM THIS
 SUBMITTAL AND PROVIDE AT INSPECTION; THEY DO REQUIRE
 PLAN REVIEW.
  
 2. ONLY ONE SET OF THE SIGNED AND SEALED DRAWINGS WERE
 SUBMITTED (DELEGATED ENGINEERING; STEEL STAIRS). PLEASE
 NOTE THAT THE BOTTOM RISER IS SHOWN GRAPHICALLY AS
 SMALLER THAN THE OTHER RISERS (FBC B 1009.7.4), AND ONE
 DIMENSION APPEARS TO SHOW A 7 5/8" RISER DIMENSION
 (SHOULD BE 7" MAX, FBC B 1009.7.2).
  
 A COMPREHENSIVE PLAN REVIEW IS NOT PERFORMED ON
 DELEGATED ENGINEERING AS THE ENGINEERING IS TO COMPLY
 WITH THE FLORIDA BUILDING CODE AND THE
 APPROVED/REVIEWED PLAN. DEVIATION FROM THE PLANS AND/OR
 FBC IS TO BE SUBMITTED AS A REVISION FROM THE DESIGNER
 OF RECORD. THEREFORE, AFTER TWO ADDITIONAL SETS OF
 STAIR DELEGATED ENGINEERING ARE SUBMITTED, THIS WILL BE
 ISSUED WITH PROVISO:
  
 PROVISO:
 INSTALLATION TO BE IN ACCORDANCE WITH THE REVIEWED
 PLANS (PERMIT DOCUMENTS) PERMITTED UNDER MASTER PERMIT
 #15020937 AND FBC 2014. ANY DEVIATION FROM THE ISSUED
 MASTER PERMIT OR FBC 2014 IS REQUIRED TO BE SUBMITTED
 AS A REVISION, PREPARED BY DESIGNER OF RECORD.
  
 3. WHEN RESUBMITTING, REMOVE OLD SHEETS (IN THIS CASE,
 THE SHOP DRAWINGS) AND PUT TOGETHER THREE IDENTICAL
 COLLATED SETS OF ENGINEERING ONLY FOR SUBMITTAL
 ISSUANCE.
  
  