Plan Review Notes
Plan Review Notes For Permit 17100228
Permit Number 17100228
Review Stop E
Sequence Number 1
Notes
Date Text
2017-10-16 07:16:19FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE DISCONNECT SWITCH AT SIGN LOCATION. NEC 600.6
  
 PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC CE 405.2.4
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL
 HAVE AUTOMATIC CONTROLS TO
 TURN OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS
 SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING
 PROGRAMING DURING A LOSS OF POWER FOR A MINIMUM OF 10
 HOURS. FBC-EC 405.2.4
  
  