2017-10-21 12:44:261ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BRANCH DRAIN FOR KITCHEN SHALL CONNECT DOWN
 STREAM OF THE BRANCHDRAIN FOR THE BATHROOMS IT SHALL
 NOT CONNECT TO WATER CLOSET DRAIN. PER FBC PL P3108.1
  
 2. THE SANITARY ISOMETRIC DRAWING SHOWS A HORIZONTAL
 DRY VENT CONNECTED AT THE SHOWER IN MASTER BATH
 HORIZONTAL DRY VENT ARE NOT ALLOWED. PLEASE REMOVE FROM
 FLOOR PLAN AND RISER.PER FBC PL P3104.3 AND P3104.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  