2017-10-21 12:44:26 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. THE BRANCH DRAIN FOR KITCHEN SHALL CONNECT DOWN | | STREAM OF THE BRANCHDRAIN FOR THE BATHROOMS IT SHALL | | NOT CONNECT TO WATER CLOSET DRAIN. PER FBC PL P3108.1 | | | | 2. THE SANITARY ISOMETRIC DRAWING SHOWS A HORIZONTAL | | DRY VENT CONNECTED AT THE SHOWER IN MASTER BATH | | HORIZONTAL DRY VENT ARE NOT ALLOWED. PLEASE REMOVE FROM | | FLOOR PLAN AND RISER.PER FBC PL P3104.3 AND P3104.4 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|